OPERATION
6
87
RM640
www.honeywellprocess.com
34-VF-25-131 iss.1 GLO Feb 2019 US
C
–
Full Setup menu
Menu No. Function
Function description
Selection list
Default
C1 Install. Parameters
C1.1
Tank Type
The conditions in which the device is used. If
the surface of the product is flat, select
"Flat surface". If there is a slightly uneven
surface, select "Medium slope". If the
surface has a steep slope, select "Steep
slope".
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
Flat Surface, Medium
Slope, Steep Slope
Steep Slope
1
C1.2
Tank Height
Tank height is the distance from the flange
face/thread stop of the process connection
to the tank bottom. If you use the device for
an LPR (open-air) application, this value is
the maximum distance that the device must
measure (the measuring range).
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Operator
min-max:
0.0...100.00
+03
mm /
0.0...2362.2
¨
/
0.0...196.85 ft
20000 mm
/ 787.402
¨
/ 65.617 ft
1
C1.5
Blocking
Distance
The distance from the flange facing or the
thread stop to the top limit of the measuring
range (a zone given by the user where it is
not possible to measure). We recommend a
minimum blocking distance of 300 mm / 12
¨
below the bottom of the antenna. If the
distance is less than the blocking distance,
the device continues to show the blocking
distance on the display screen.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
0.0...5000.0 mm /
0.0...196.85
¨
/
0.0...16.404 ft
Antenna length
+ antenna
extension
300 mm / 12
¨
C1.6
Time Constant
Using this function, the device processes
several measurement readings to filter out
disturbances. Increasing the time constant
will smoothen the integrated readings,
decreasing will roughen the readings. s =
seconds.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
0....100.0 sec (seconds)
30 s
C1.7
Antenna Type
The type of antenna attached to the device. If
you change the antenna, this setting will
have an effect on C1.2 Tank Height and C1.5
Blocking Distance.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
Metallic Horn (DN80),
Metallic Horn (DN100),
Metallic Horn (DN200),
Drop (PP, DN80), Drop
(PP, DN100), Drop (PP,
DN150); Drop (PTFE,
DN80), Drop (PTFE,
DN100), Drop (PTFE,
DN150)
As specified in
the customer
order
C1.8
Antenna
Extension
Optional antenna extension. These are
attached between the flange and the
antenna. Each segment is 105 mm / 4.1
¨
long.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
0.0
…
1050 mm /
0.0...41.339
¨
/
0.0...3.4449 ft
0 mm /0
¨
1
C1.9
Distance piece
Optional distance piece between the
converter and the process connection. This
is for the high-temperature version of the
device. Each segment is 105 mm / 4.1
¨
long.
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
Minimum access level to change the
setting:
setting:
setting:
setting: Expert
min-max:
0.0
…
2000 mm /
0.0...78.740
¨
/
0.0...6.5617 ft
0 mm / 0
¨
1
Содержание RM640
Страница 4: ...4 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ABOUT THIS DOCUMENT RM640 ...
Страница 20: ...1 SAFETY INSTRUCTIONS 20 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 56: ...4 ELECTRICAL CONNECTIONS 56 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 120: ...6 OPERATION 120 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 164: ...9 DESCRIPTION OF HART INTERFACE 164 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 182: ...10 APPENDIX 182 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 183: ...APPENDIX 10 183 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...