DESCRIPTION OF HART INTERFACE
9
153
RM640
www.honeywellprocess.com
34-VF-25-131 iss.1 GLO Feb 2019 US
9.3.2 Multi-Drop connection (2-wire connection)
Up to 63 devices may be installed in parallel (this signal converter and other HART
®
devices).
For an illustration of multi-drop networks, refer to
Multi-drop networks
on page 55.
For data on communication in multi-drop mode, refer to
HART
®
network configuration on page
104.
9.4 HART
®
device variables
The HART
®
dynamic variables PV (Primary Variable), SV (Secondary Variable), TV (Third Variable)
and QV (Fourth Variable) can be assigned to any of the device variables.
The HART
®
dynamic variable PV is always connected to the HART
®
current output which is, for
example, assigned to level measurement.
9.5 Field Communicator 475 (FC 475)
The Field Communicator is a hand terminal from Emerson Process Management that is
designed to configure HART
®
and Foundation Fieldbus devices. Device Descriptions (DDs) are
used to integrate different devices into the Field Communicator.
9.5.1 Installation
System and software requirements for the Field Communicator
•
System card that includes the "Easy Upgrade Option"
•
Field Communicator Easy Upgrade Programming Utility
•
HART
®
Device Description file
For more data, refer to the Field Communicator User
’
s Manual.
HART
®
device variable
Code
Type
sensor value
0
linear
level
1
linear
distance
2
linear
reflection
3
linear
level linearization
1
4
linear
volume conversion
2
5
linear
mass conversion
2
6
linear
distance linearization
1
7
linear
ullage volume conversion
2
8
linear
ullage mass conversion
2
9
linear
1
This HART
®
device variable is available if you created a linearization table in the conversion menu
2
This HART
®
device variable is available if you created a strapping table in the conversion menu
CAUTION!
The Field Communicator cannot be used to correctly configure, operate or read data from the
device unless the Device Description (DD) file is installed.
Содержание RM640
Страница 4: ...4 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ABOUT THIS DOCUMENT RM640 ...
Страница 20: ...1 SAFETY INSTRUCTIONS 20 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 56: ...4 ELECTRICAL CONNECTIONS 56 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 120: ...6 OPERATION 120 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 164: ...9 DESCRIPTION OF HART INTERFACE 164 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 182: ...10 APPENDIX 182 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...
Страница 183: ...APPENDIX 10 183 RM640 www honeywellprocess com 34 VF 25 131 iss 1 GLO Feb 2019 US ...