CONFIGURATION AND ANALYSIS SOFTWARE ENSUITE
Information for general use
Rev. M / 73023639
185
GasLab Q2
Time-controlled actions:
The enCore device provides following time-related events of a signal
type in the export branch
Basic System
–
or standard time
Time Service
–
Timer events
:
Every second
/
Every <2, 3, 5, 10, 15, 20, 30> seconds
Every minute
/
Every <2, 3, 5, 10, 15, 20, 30> minutes
Every hour
/
Every <2, 3, 4, 6, 12> hours
Every day (at midnight)
Every Sunday (at midnight)
Every Monday (at midnight)
Every month (midnight on 1st)
Special case: Trigger for a longer cycle duration is activated first
Event signals in a second rhythm are formed relative to a full minute and event
signals in a minute rhythm are formed relative to a full hour.
For example:
Every other minute
e.g., 12:02:00
…
12:04:00
…
12:06:00
…, etc.
Every 3 minutes
e.g., 12:03:00
…
12:06:00
…
12:09:00
…, etc.
This means that immediately after the device is restarted and until a cyclic event
signal is first triggered the time depends on the boot time and may be shorter than
the associated cycle. This special case can only occur once immediately after the
device is restarted.
Example:
If the enCore device is switched on at 12:02:30 and the signals
Every
other minute
and
Every 3 minutes
are used as triggers, at system time
12:03.00, the signal
Every 3 minutes
is formed and only subsequently at
12:04.00 is the signal
Every other minute
formed.
Export values based on the system time in the export branch
Basic System
–
Time
Service
–
Contract hour: <single contract/two contracts>
:
(initial contract or single contract)
Contract hour (numeric)
Every day (at contract hour)
Every Sunday (at contract hour)
Every Monday (at contract hour)
Every month (at contract hour on 1st)
(second contract
–
optional)
Contract
hour 2 (numeric)
Every day (at 2nd contract hour)
Every Sunday (at 2nd contract hour)
Every Monday (at 2nd contract hour)
Every month (at 2nd contract hour on 1st)