EK280
Application Manual
143
Example parameters:
−
Activate the button
"
Transfer values to device
", so that the modified values are transferred into
the EK280.
−
Make sure that the FE260 is connected to the EK280 in accordance to
−
Turn on the FE260 power supply.
−
Now under “
Parameters
” >
“
Interfaces
”
>
“
Call time windows
”
open one of the time windows 5 or 6.
After opening the time window, the Ethernet adapter is automatically parameterized by the EK280
(V2.40).
After approximately 30s, the Ethernet adapter is configured. Check the connection status of the appropriate
connection profile (time window 5 = connection) to verify that parameterization was successful (Setpoint =
"4: The interface is ready…").
7.4.10.3 Checking accessibility
−
Make sure that the Ethernet connecting cable of the FE260 is connected to the network (LAN).
−
In order to be able to verify the Ethernet card configuration, have your network administrator execute
a ping command to the corresponding IP address (e.g., ping 192.168.0.5.). This will ensure that the
IP address is registered within the network and valid.
7.4.10.4 Retrieving data with enSuite
h) a) Opening the test time window for the following test retrievals with enSuite
i
The test time window only needs to be open if none of the time windows 5 to 6 is currently open.
i) b) Test retrieval via the network.
−
If the communication link to the EK280 is via the optical interface, press the "
Interrupt connection
" or
the "
Break all connections
" icon to terminate the communication link between enSuite and the
EK280 and then wait for the "o" top left of on the EK280 display to stop flashing.
−
Now set up the communication link from enSuite to EK280 via the Ethernet adapter. (
Setting up the communication link to EK280 via a network (TCP/IP)
−
Once the communication link is set up, you can carry out checks, for instance view certain
parameters. If not already displayed automatically, click on the left-lower part of the navigation
window on “Parameterize online”, then click on the plus sign next to the menu "Parameter" and on
the sub-item
−
In enSuite press the “
Disconnect
” symbol or
“
Disconnect from all devices
”
to end the test retrieval.