![Honeywell Elster EK280 Скачать руководство пользователя страница 101](http://html.mh-extra.com/html/honeywell/elster-ek280/elster-ek280_applications-manual_151826101.webp)
EK280
Application Manual
99
−
Press the
“Transfer changes to device
” icon at the top of the enSuite window.
The EK280 can now be accessed via the modem for the duration set.
−
In enSuite, press the “
Disconnect
” or “
Disconnect from all devices
” icon to terminate the optical
interface communication link between enSuite and the EK280.
b) Test retrieval via the TCP/IP network
Establish the communication link between enSuite and the EK280 via the network.
(
3.3 Setting up the communication link to EK280 via a network (TCP/IP)
−
Once the communication link has been established, you can carry out checks, for instance view
certain parameters. To do this, press “
Navigation
” on the left-hand side of the enSuite window and
then “
Parameterize online
” at the bottom of the navigation window, then click on the plus sign next to
“
Parameters
” and then its subsections.
−
In enSuite, press the “
Disconnect
” or “
Disconnect from all devices
” icon in order to end the test
retrieval.
7.2.6 Retrofitting the internal Ethernet interface
Attention! Danger of death!
The mains voltage must be switched off before opening the housing of the EK280. Ensure it is not
turned back on and verify that there is no voltage.
Attention
The internal modem may only be retrofitted in the non-hazardous area or in ex-zone 2, but not in
ex-zone 0/1!
−
Attach the Ethernet module to the
right socket connector and secure it to
the PCB housing with the screws
provided.
Once you have installed the Ethernet module in the EK280
−
attach the network cable (
) and
−
parameterize the Ethernet module (