EK280
Application Manual
121
(p. 118).
Here the GPRS resp. UMTS modem in the EK280 functions as a TCP-Server and may be addressed by a
TCP client that is listed in its retrieval software through a static IP address. To allocate a static IP to the
modem during the setup of the GPRS resp. UMTS session, they must (together with their network provider)
maintain a virtual private network (VPN) which must be enabled on the SIM used in the modem.
Prerequisites for process described below:
−
The FE260 is connected and configured as described in
−
The modem installed in the FE260 is suitable for TCPserv operation and is supported by the
software version installed in the connected EK280 (refer to table on
−
The SIM card is inserted and unlocked as described in
−
The SIM card may be unlocked by entering the correct PIN in accordance with
7.4.6.1 EK280 Parametrization
i
A modem parameterized for TCPserv operation can still be called via the CSD
(GSM operation
). However, a CSD connection cannot consist of a TCP
connection at the same time: only one after the other!
i
For parameterization of the EK280 you need a connection cable for the optical interface as well
as the enSuite program. enSuite can be downloaded free of charge from the Honeywell website
in the "Software Downloads" section:
www.elster-instromet.com/en/software-downloads
a) Closing the time windows
In order that the parameterization works correctly the time windows 5 and 6 must be closed. To do this:
−
Connect a PC with enSuite installed to the EK280 optical interface using the connection cable.
−
Start enSuite and set up the communication link to the EK280.
(
3.1 Setting up the communication link to the EK280 via optical interface
−
Select "
Navigation
" on the left-hand side and then "
Parameterize online
" at the bottom of the
navigation window.
−
In the top of the device window open the path "
Parameters
" > "
Interfaces
" by clicking on the relevant
plus signs, and then select "
Call time windows
".
−
In call windows 5 and 6 set start and end to the same value for each one and then select the
"Transfer changes to device" icon at the top of the enSuite window.
−
Then wait a minute, for any communications activity in progress on the EK280 to be safely stopped.
b) Sending parameter file
−
Depending on the modem module fitted to the FE260 and the loaded modem application (this can be
determined from the modem sticker,
7.4.6.2 Parameterization of the GPRS/TCPserv
, p. 124) send one of the following parameter files to K280 (
26
CSD=Circuit Switched Data, circuit-switched data service in the case of mobile telephony.