EK280
Application Manual
129
i
With a field strength below 50% data transfer issues may be encountered. Adjusting the antenna
position can improve field strength in most cases.
7.4.6.4 Retrieving data with enSuite
−
If the call window is not open (
(p. 121), section c), a
unique “Test” time window can be set up for verification purposes:
a) Opening the test time window for the following test retrievals with enSuite
i
The test time window only needs to be open if none of the time windows 5 to 6 is currently open.
−
If the communication link to the EK280 via the optical interface is not set up, it must be created.
(
3.1 Setting up the communication link to the EK280 via optical interface
−
Select "
Navigation
" on the left-hand side of the enSuite window and then "
Parameterize online
" at
the bottom of the navigation window.
−
In the top of the navigation window click first on the plus sign next to "
Parameters
", then on the plus
sign next to "
Interfaces
" and then on "
Terminal interface
".
−
Click on the "
0
" value next to "
Test call acceptance window
" in the right-hand side of the window and
enter a duration in minutes (i.e. 10), for the test time window for the test retrieval to remain open.
−
Press the "
Transfer changes to device
" icon at the top of the enSuite window.
The EK280 is now available via the modem for the duration set.
−
In enSuite press the "
Disconnect
" symbol or "
Disconnect from all devices
" to end the test retrieval.
b) GSM-CSD Test retrieval via the modem
−
Set up the modem communication link from enSuite to the EK280.
(
3.2 Setting up the communication link to EK280 via a modem
−
Once the communication link is set up, you can carry out checks, for instance view certain
parameters. To do this press "
Navigation
" on the left-hand side of the enSuite window and then
"
Parameterize online
" in the bottom of the navigation window, then click on the plus sign next to
"
Parameters
" and then its subsections.
−
In enSuite press the "
Disconnect
" symbol or "
Disconnect from all devices
" to end the test retrieval.
c) GPRS-TCPserv Test retrieval via the modem
Set up the modem communication link from enSuite to the EK280.
(
3.3 Setting up the communication link to EK280 via a network (TCP/IP)
Once the communication link is set up, you can carry out checks, for instance view certain
parameters. To do this press "
Navigation
" on the left-hand side of the enSuite window and then
"
Parameterize online
" in the bottom of the navigation window, then click on the plus sign next to
"
Parameters
" and then its subsections.
In enSuite press the "
Disconnect
" symbol or "
Disconnect from all devices
" to end the test retrieval.