USER GUIDE
FALCON
93
EN2Z-0962GE51 R0715
I/O Pull-up Resistor Handling
The following diagram and table shows the pull-up resistor handling when using XFL
und XFC modules with the Excel Web controller.
A
D
18.2 kOhm
(pull-up)
100 k
Ù
100 kOhm
5 V
A
D
24.9 kOhm
(pull-up)
150 k
Ù
49.9 kOhm
10 V
Case 1
Case 2
Fig. 15. Input circuit diagram
Table 1. Pull-up resistor handling
device
pull-up
input
circuit
diagram
load-free voltage
voltage hardware
Can be
deactivated
(1)
configured
by DIP
switch
configured
by plug-in
activated
for DI on
AI
(2)
with NTC
or low-
impedance
input
for voltage
input or
high-
impedance
input
XFL521A/B
10 V
optional
switch-off
YES
NO
YES
YES
case 1
8.89 V
0 V
Smart I/O
XFC
5 V
case 3
5 V
(1
by using CARE ≥ 7.01, by selecting I/O characteristic "No Pull-up" in the analog input datapoint.
(2
automatically by using CARE ≥ 7.01
I/O Initializiation
Input Datapoints (AI, BI)
Start
BACnet input datapoints will be initialized with the value ´zero`. After initialization,
the field devices values will be read. If no value is received after the set heartbeat
time (default = 60 s), the Excel Web controller polls the input module.
Alarm behavior
At the beginning, all input points are not in alarm by default except those of which
input values have caused an alarm.
After the start alarm time has expired, an alarm will be saved in the alarm buffer,
shown in the alarm list and reported to the EBI as long as the alarm exists.
Restart, Reset, Power Failure,
Application- and Firmware Download
The following values/statuses will always be saved in the battery retentive RAM and
restored after restart, reset or power failure of the Excel Web controller.
•
Runtime counter
•
Last reset time
•
Elapsed active time
•
Out of Service flag
•
Points in manual operating mode
The advantage here is that these values will survive an application and
firmware download.
When an Excel Web controller is replaced, these values cannot be transferred
to the new Excel Web controller.
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...