Notification Class Manager
The notification class manager in CARE is used for adapting the alarming to the EBI
central and 3
rd
party BACnet clients according to the requirements.
This is done by creating, editing and deleting notification class objects.
Notification
class objects will be assigned to datapoints in order to enable alarming for
datapoints.
About Notification Class
Notification class objects represent and contain information required for the
Object Types
distribution of event notifications within a BACnet system.
Notification Classes are useful for event-initiating objects that have identical needs
in terms of how their notifications should be handled, what the recipient(s) for their
notifications should be, and how they should be acknowledged.
A notification class defines how event notifications shall be prioritized in their
handling according to TO-OFFNORMAL, TO-FAULT, and TO-NORMAL events;
whether these categories of events require acknowledgment (nearly always by a
human operator); and what recipient devices (e.g. Excel Web HTML Interface, EBI)
or processes should receive notifications.
The purpose of prioritization is to provide a means to ensure that alarms or event
notifications with critical time considerations are not unnecessarily delayed. The
possible range of priorities is 0 - 255. A lower number indicates a higher priority.
Priorities may be assigned to TO OFF-NORMAL, TO FAULT, and TO NORMAL
events individually within a notification class.
In CARE, the alarms/event notifications are prioritized by default as follows:
Transitions
Event / Alarm Category
To Normal
To Off-Normal
To Fault
Urgent (range 0…84)
83
0
42
High (range 85…169)
168
86
127
Low (range 170…250)
250
171
210
NOTE: The CARE ranges slightly differ from the event / alarm priority ranges
defined in the BACnet standard which affects the associated network
priority (see “Alarm and Event Priority Classification” section below).
The transitions have the following denotation:
Back To-Normal
The alarm is going to normal state, that is, the value of the datapoint remains under
the high limit, or exceeds the low limit.
To Off-Normal
The alarm reaches off-normal state, that is, the datapoint value exceeds the high
limit, or remains under the low limit.
To Fault
The alarm originates in a fault such as sensor break, etc. See “Point Flag
Indications” for details.
The purpose of acknowledgment is to provide assurance that a notification has been
acted upon by some other agent, rather than merely having been received correctly
by another device. In most cases, acknowledgments come from human operators.
TO OFF-NORMAL, TO FAULT, and TO NORMAL events may, or may not, require
individual acknowledgment within a notification class.
It is often necessary for event notifications to be sent to multiple recipients or to
different recipients based on the time of day or day of week. Notification Classes
may specify a list of recipients, each of which is qualified by time, day of week, and
type of handling. A recipient is specified by a set of days of the week (Monday
through Sunday) during which the recipient is considered viable by the Notification
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...