Event
Shows the transition types that can be selected for reporting.
Reporting
Check the transition event(s) that should be observed and cause an event
notification to the recipient (device or email addressee).
−
Back-To Normal
An event notification is sent if the acknowledgement is sent after the time
delay has been expired.
−
To-Off Normal
An event notification is sent if the acknowledgement is missing within the
time delay
To Fault
This option has no function.
Ackn.
Shows the Acknowledged status and allows acknowledgement.
The acknowledged status (checked or unchecked), firstly depends on the
Ack Required
setting of the notification class in CARE. In CARE, for each
transition type you can define wthether an acknowledgement ist required or
not. Secondly, the possibility to change the Ackn. status depends on the
reporting status of the transition (enabled or disabled) here.
Last Transition
Shows the date when the last transition has occurred.
Event Parameters
•
Event Type
The event type is ´change of bitstring`.
•
Bit Mask
Shows the transition event(s) that are checked for acknowledgement.
•
Bit String(s)
Shows the possible logical values (true, false, CARE verifies with negative
logic for the false condition) resulting from the comparison of the selected
transition event(s) and the underlying bitstring mask. An event enrollment
alarm will be sent, if the transition event will
not
be acknowledged within the
delay time.
•
Time delay
Enter a time delay in sec. The event enrollment alarm will be sent if the
transition event has
not
be acknowledged within the delay time.
For details on the options below, please refer to the datapoint desriptions in the
CARE User Guide.
3.
Click SUBMIT button, and/ or viewing general information of the event
enrollment, clicki the
General
tab.
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...