FALCON
USER GUIDE
EN2Z-0962GE51 R0715
192
(Applies to AO, AV, BO, BV, MO, and MV datapoint types only)
1.
In the
Details
dialog box of the selected datapoint, select the
Command
Priorities
tab.
Here you can view the command priority levels and enter/change the relinquish
default value.
The priority list has descending priority. The value on the highest priority level is
written to the present value.
•
Relinquish Default
This value will be written to present value, if all values in the priority list are
invalid.
Enter relinquish default value into the field.
3.
To save changes, click the SUBMIT button.
For detailed description, please refer to the "Relinquish Default" and "Priority Level"
sections.
View / Edit Event Enrollment Alarming
Event enrollment alarming can be used for observing the following datapoint
properties:
•
Present value
•
Acknowledged transitions (datapoint alarms)
•
Status flag conditions
•
Elapsed active time / count limits
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...