FALCON
USER GUIDE
EN2Z-0962GE51 R0715
202
Algorithmic Reporting
•
Notification Class
Shows the name of the notification class. The value in brackets is the
BACnet object ID of the notification class.
•
Notify Type
Shows the notify type. Defaults to ´event`. For details, see Notify Type
property description
•
Event State
Shows the event state. For details, see Event State property description.
•
Transitions
Here the following data about transitions are shown:
Event
Shows the transition types that can be selected for reporting.
Reporting
Check the transition event(s) that should be observed and cause an event
notification to the recipient (device or email addressee).
−
Back-To Normal
An event notification is sent if the elapsed active (elapsed) runtime,
respectively number of state count changes takes a value within the high
or low limit after the time delay has been expired.
−
To-Off Normal
An event notification is sent if the elapsed active (elapsed) runtime value,
respectively number of state count changes value exceeds the high or low
limit within the alarm.
To Fault
This option has no function.
Ackn.
Shows the Acknowledged status and allows acknowledgement.
The acknowledged status (checked or unchecked), firstly depends on the
Ack Required
setting of the notification class in CARE. In CARE, for each
transition type you can define wthether an acknowledgement ist required or
not. Secondly, the possibility to change the Ackn. status depends on the
reporting status of the transition (enabled or disabled) here.
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...