USER GUIDE
FALCON
55
EN2Z-0962GE51 R0715
−
Back To-Normal
The alarm is going to normal state, that is, the value of the datapoint
remains under the high limit, or exceeds the low limit.
−
To Fault
The alarm originates in a fault such as sensor break, etc. (depends on
point type).
IMPORTANT
Always enable both options, ´To Off-Normal` and ´Back To-Normal`,
otherwise you will miss one of the corresponding alarms.
In the Excel Web HTML Interface, the transition type is selected by checking the
Reporting
checkbox.
See also "Transition Events" and “Alarm and Event Priority Classification” sections.
Event Enrollment
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
x
X
Equivalent
The primary purpose of the Event Enrollment object is to define an event and to
provide a connection between the occurrence of an event and the transmission of a
notification message to one or more recipients. The Event Enrollment object
contains the event-type description, the parameters needed to determine if the event
has occurred (Algorithmic Change Reporting), and a device to be notified.
Alternatively, a Notification Class object may serve to identify the recipients of event
notifications. A device is considered to be "enrolled for event notification" if it is the
recipient to be notified or one of the recipients in a Notification Class object
referenced by the Event Enrollment object. Event Enrollment objects are the basics
for algorithmic change reporting.
See also "Bit Mask" section.
See also "Bit String(s)" section.
See also "Time Delay" section.
Event State
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
Equivalent
For any datapoint type, an application and/or product specific value range is defined
in which the point is in the operating (event) state ´Normal`. If the point value has
changed due to exceptional situations, the event state of a datapoint can be either
´Off-Normal` or ´Fault`.
The event states can be shortly described as follows:
Normal
Point is in normal operating state.
Off-Normal
Point value is out of normal range.
Fault
Point is prevented from proper operation. Point value can be in normal or out of
normal range. Due to the maloperation of the point, the value is unreliable.
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...