
USER GUIDE
FALCON
247
EN2Z-0962GE51 R0715
RESULT:
On the
Event Enrollments
tab, you can select event enrollments
to enable the controller´s system status alarming and the
alarming of the controller´s Email alarming:
3.
To enable event enrollment alarming for the controllers email alarming, click the
EmailAlarming
link. To enable event enrollment alarming for the controller´s
system status, see “Enable Event Enrollment Alarming for Controller System
Status” section.
RESULT:
After selecting the
System Status
event enrollment, the
Event
Enrollment Details
dialog box displays. The
Alarming
tab is
selected by default. Here the following algorithmic reporting
settings defined in CARE are displayed:
•
Notification Class
•
Notify Type
•
Event State
•
Transitions (Acknowledged status and time and date of last
transition)
•
Event Type
•
BACnet Property State
•
BACnet Device State(s) (=Off-Normal-States)
You only can select the transitions to be reported and set the
delay time.
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...