date/time is reached and ends at stop date/time. During trending the status is
active as indicated by the checked
Active
option.
r. To stop Trending, click the DISABLE LOGGING button
(Status: Enabled=unchecked, Active=unchecked).
Start and Stop Date/Time is defined under
Trending Start / Stop Date
and
Time
.
Trend Parameter
Here you can define the time interval in which a parameter should be logged
s. Enter the time in h:m:s in the
Log every
fields.
NOTE: For the log interval setting, the following guideline should be
considered:
Based on the default log interval for time-based trending (1 minute)
and the max. no. of trend log objects (125), a maximum of 2 trend
records per second can be created:
125/60 = 2 (limiting factor)
For value-based trending, the default log interval should be estimated
roughly by noting the no. of value changes which occurred within an
appropriate time period.
Any calculations should result in a limiting factor of less than 2 (trend
records per second).
Example:
You have a trend setting of 40 trend log objects with 1 trend record per
minute plus 20 trend log objects with 1 trend record per 2 minutes.
The result is an addition of the values as follows:
40/60 + 20/120 = 0.833 => less than 2
Trending Start / Stop Date and Time
Here you can define the time range (start and stop date/time) of the trending.
To define the time range, do the following:
t. Click the
Start Date
checkbox and enter the start date into the fields or select
date by clicking the BROWSE button.
u. In the
Time
fields enter the time
NOTE:
If the checkbox is unchecked, the fields are disabled. This means, that trending
will occur on any date up to and including the end date.
v. Click the
Stop Date
checkbox and enter the end date into the fields or select
date by clicking the BROWSE button.
w. In the
Time
fields enter the time
NOTE:
If the checkbox is unchecked, the fields are disabled. This means, that trending
will occur on any date from the start date on.
NOTE:
If both fields are disabled, trending will occur instantly and all the time.
If clicking the ENABLE LOGGING button enables the trend logging, the trending
starts as soon as the start date/time is reached and ends at stop date/time.
During trending the status is active as indicated as checked Active.
Stop of Trending is done by clicking the DISABLE LOGGING button (Status:
Enabled=unchecked, Active=unchecked).
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...