
FALCON
USER GUIDE
EN2Z-0962GE51 R0715
196
Purpose
Allows observing the acknowledgement behavior of a user for To-Off-Normal and
To-Fault transition events of the datapoint. CARE checks whether a transition event
has been acknowledged or not. If a transition event has not been acknowledged
within a definable delay time, an alarm based on an event enrollment (event
enrollment alarm) is sent to a supervisory recipient, for example EBI.
Procedure
1.
In the
Details
dialog box of the selected datapoint, select the
Event Enrollments
tab.
Here you can select different event enrollments for viewing and edting. Each
event enrollment is displayed as link. By default, event enrollments have the
following naming convention <EE = event enrollment> <datapoint type
abbreviation> <event enrollment type>, for example EE ai. AckedTransitions.
2.
To view/edit an event enrollment, click the event enrollment, for example EE ai.
AckedTransitions. The
Details
dialog box for the selected event enrollment
displays. The
Alarming
tab is selected by default.
Algorithmic Reporting
•
Notification Class
Shows the name of the notification class. The value in brackets is the
BACnet object ID of the notification class.
•
Notify Type
Shows the notify type. Defaults to ´event`. For details, see Notify Type
property description
•
Event State
Shows the event state. For details, see Event State property description.
•
Transitions
Here the following data about transitions are shown:
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...