USER GUIDE
FALCON
49
EN2Z-0962GE51 R0715
The following table shows examples of instances, which CARE automatically
assigns to the corresponding BACnet objects while they are created:
The instance number in combination with the BACnet object type information is one
method in creating and adding a 3
rd
party BACnet device to the BACnet bus (see
also "BACnet Object ID" section).
This information must be provided by or to the project engineer/vendor who is
responsible for the 3
rd
party BACnet device to be added to the CARE project, or who
is responsible for integrating the Excel Web controller into a 3
rd
party BACnet
system.
NOTE: In Europe it is common using the EDE data format for interchanging
information between BACnet objects. For further information, please
access the BACnet Interest Group Europe e.V. at:
BACnet Object (Type)
Datapoint Type
AI AO AV BI BO BV MI MO MV PC RI RO
User Interface
HTML Interface
CARE
Editing
-
Equivalent
The BACnet object type is part of the internal BACnet addressing in every BACnet
system (BACnet communication). The BACnet object type is not visible in the Excel
Web HTML Interface and the user does not need the BACnet object type in order to
operate the Excel Web controller.
In the BACnet standard, BACnet objects are classified in types.
Example: Analog inputs are of BACnet object type "analog input(0)", binary inputs
are of BACnet object type "binary input(3)", devices such as the Excel web
controller and 3
rd
party BACnet devices are of BACnet object type
"device(8)”
The BACnet object type information in combination with the instance number is one
method in creating and adding a 3
rd
party BACnet device to the BACnet bus (see
also "BACnet Object ID" section).
This information must be provided by or to the project engineer/vendor who is
responsible for the 3
rd
party BACnet device to be added to the CARE project, or who
is responsible for integrating the Excel Web controller into a 3
rd
party BACnet
system.
The BACnet Object type defaults according to the BACnet convention are as follows
(see next page):
Object Type
Instance Number
Analog input 1
1
Analog input 2
2
Analog input 3
3
Analog input 4
4
Analog input 5
5
Binary input 1
1
Binary input 2
2
Binary input 3
3
Binary input 4
4
Binary input 5
5
Содержание Centraline FALCON
Страница 1: ...FALCON User Guide Copyright 2015 Honeywell GmbH All Rights Reserved EN2Z 0962GE51 R0715 ...
Страница 2: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 ...
Страница 4: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 4 ...
Страница 9: ......
Страница 11: ...USER GUIDE FALCON EN2Z 0962GE51 R0715 7 ...
Страница 12: ...FALCON USER GUIDE EN2B 0962GE51 R0715 8 ...
Страница 24: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 20 Fig 7 Open BACnet LON System Architecture for Plant Control ...
Страница 25: ...USER GUIDE FALCON 21 EN2Z 0962GE51 R0715 Fig 8 Open BACnet LON System Architecture for Room Control ...
Страница 77: ...USER GUIDE FALCON 73 EN2Z 0962GE51 R0715 ...
Страница 113: ...USER GUIDE FALCON 109 EN2Z 0962GE51 R0715 Fig 26 Alarm behavior of pulse converter datapoint ...
Страница 262: ...FALCON USER GUIDE EN2Z 0962GE51 R0715 258 ...