Document No: C-61-00003-3
piece is removed
4
If the UAM is in manual restart mode, OSSD remains in
OFF-state when UAM is restarted
5
If the UAM is in automatic restart mode, OSSD signal
switches from ON-state to OFF-state when the test piece is
placed inside the protection zone and switches from
OFF state to ON state when the test piece is removed
6
If the UAM is in automatic restart mode, OSSD remains in
OFF-state when UAM is restarted with obstacle inside the
protection zone
7
If the start interlock function is configured, starting the
UAM without placing the test piece in protection zone
causes the OSSD signal to remain in OFF-state until the
RESET signal is provided
8
If the muting function is configured, UAM terminates the
muting (OSSD switches to OFF-state) when the test piece
is placed inside the protection zone other than the muting
area even though the muting conditions are fulfilled.
9
If the muting function is configured, UAM does not switch
to mute state when the muting input sequence is different
than the specified sequence.
10
If the muting function is configured, UAM does not switch
to mute state when the time interval between two muting
inputs exceeds the specified time interval
11
If the muting function is configured, the override function
is terminated when the override period exceeds the
specified override period
12
If the reference monitoring function is configured,
displacement of the reference boundary structures or UAM
should cause the OSSD to switch to OFF-state when
displacement exceeds the allowable tolerance. This is
applicable especially if the angle of approach exceeds ±30º
from the detection plane
13
If the area sequence function is configured, OSSD switches
to OFF-state if area switching sequence is different than
the configured sequence.
Note: Stop using the UAM when any check item is marked NO.
8.3 Daily inspection
Table 8-3 shows an example of items that should be checked during daily inspection.
Table 8-3 Daily inspection list example
No.
Check item
Condition
Remark
Yes
No
1
The OSSD signal switches from ON state to OFF state
when test piece is placed inside the protection zone
2
The OSSD signal remains in OFF state when the test piece
Содержание UAM-05LP
Страница 1: ... Document No C 61 00003 3 ...
Страница 104: ... Document No C 61 00003 3 Figure 7 33 b Function Figure7 33 c Area ...
Страница 107: ... Document No C 61 00003 3 Figure 7 36 a Project report tab Figure 7 36 b Error report tab ...
Страница 148: ... Document No C 61 00003 3 13 External dimension 13 1 UAM 05LP ...
Страница 149: ... Document No C 61 00003 3 13 2 Base mounting bracket ...
Страница 150: ... Document No C 61 00003 3 13 3 Rear mounting bracket ...
Страница 151: ... Document No C 61 00003 3 13 4 Cover Protection Bracket ...
Страница 152: ... Document No C 61 00003 3 14 EC Declaration of conformity ...
Страница 153: ... Document No C 61 00003 3 ...