Page 41 of 52
10.7 CONFIGURING FEATURES:
The re are two types of Features; those which are just turned ON and OFF, and those with Multiple Settings. For
ON
and OFF Features
, the
Yellow LED
is lit for ON, and not lit for OFF, and the
Yellow Button
is pressed to change the
ON / OFF setting. For
Multiple Setting Features
, the
Yellow LED
flashes a number of times to indicate the setting,
then pauses; the
Yellow Button
is used to change the selected setting. Be sure to pause for about 3 seconds after
changing the
Configuration DIP Switches
, or pressing the
Yellow Button
to see the results.
DIP SWITCH
POSITION (1-8)
FEATURE
DESCRIPTION
0000 0001
Style D/B (Class A/B) Initiating Circuits
Yellow LED
lit indicates that all Initiating Circuits (Detection
Zones) are Style D (Class A), off indicates that they are all Style
B (Class B). This Feature can be checked at any time, but must
only be changed as described in
Restore to Default
.
0000 0010
Manual Signal Silence Enable
Yellow LED
lit indicates that Manual Silence is enabled.
0000 0011
Fire Drill Enable
Yellow LED
lit indicates that Fire Drill is enabled.
0000 0100
Two Stage Operation Enabled
Yellow LED
lit indicates that the System is set for Two Stage
operation, and not lit indicates Single Stage operation.
0000 0101
Common Alarm Relay
Operation
Yellow LED
lit indicates that if the System is for Two Stage
operation, the Common Alarm Relay will only operate during the
General Alarm Stage. If not lit, the Common Alarm Relay will
operate during both Stages.
0000 0110
Output Circuit Correlations Enabled
Yellow LED
lit indicates that Output Circuits (Indicating Circuits
and Relays) operate according to any set Correlations (see
Correlation section). If the
Yellow LED
is not lit, all Output
Circuits are Common Alarm; all outputs turn on for any Alarm
Input.
0000 0111
Waterflow & Sprinkler Retard Operation
Yellow LED
lit indicates that Waterflow Retard is enabled.
0000 1000
Reserved for Future Use
0000 1001
Aux Disc & Programmable Relays
Yellow LED
lit indicates that Correlated Relays are disconnected
by Auxiliary Disconnect.
0011 1000
Show Relay Circuits
All Display Points assigned to Relay Circuits will be lit.
0000 1010
Signal Silence Inhibit Timer
Yellow LED
does not flash
=
Disabled
Yellow LED
flashes 1 time
=
1 minute
Yellow LED
flashes 2 times
=
2 minutes
Yellow LED
flashes 3 times
=
3 minutes
0000 1011
Auto Signal Silence Timer
(This timer cannot be set shorter than either
the Auto General Alarm or Signal Silence
Inhibit timers, if those timers are enabled)
Yellow LED
does not flash
=
Disabled
Yellow LED
flashes 1 time
=
5 minute
Yellow LED
flashes 2 times
=
10 minutes
Yellow LED
flashes 3 times
=
15 minutes
Yellow LED
flashes 4 times
=
20 minutes
Yellow LED
flashes 5 times
=
30 minutes
0000 1100
Auto General Alarm Timer
(Leave disabled unless the System is
configured for Two Stage operation)
Yellow LED
does not flash
=
Disabled
Yellow LED
flashes 1 time
=
5 minute
Yellow LED
flashes 2 times
=
10 minutes
Yellow LED
flashes 3 times
=
15 minutes
Yellow LED
flashes 4 times
=
20 minutes
Yellow LED
flashes 5 times
=
30 minutes
0000 1101
Audible Indicating Circuit
Evacuation Code
Yellow LED
flashes 1 time
=
Continuous
Yellow LED
flashes 2 times
=
March Time
Yellow LED
flashes 3 times
=
Temporal Code
Yellow LED
flashes 4 times
=
California Code
0000 1110
Number of Remote Annunciators
Yellow LED
flashes 0 to 8 times to indicate the number of
Remote Annunciators expected by the System.
10.8 CONFIGURING INITIATING AND INDICATING CIRCUITS:
firealarmresources.com
Содержание HCP 1000 Series
Страница 2: ...firealarmresources com...
Страница 10: ...Page 8 of 52 Fig 1A HBB 1072 Flush or Surface Enclosure Installation and Dimensions firealarmresources com...
Страница 14: ...Page 12 of 52 Fig 4 Module Mounting Locations firealarmresources com...
Страница 15: ...Page 13 of 52 Fig 4A Circuit Adder Module Mounting Details firealarmresources com...