10.2 ENTERING CON FIGURATION MO DE:
The System enters
Configuration Mode
whenever any of the
Configuration DIP Switches 2 to 8
(Switc h 1 is used
to enter W alk-Tes t Mode) are s et to a “1" or On position (top position). The
TEST / CONFIG MODE
and
COMMON
TROUBLE
LED ’s will turn on, an d the buzze r will sound. T he B uzzer m ay be s ilence d at this point.
The F ire Alarm C ontrol Pa nel is not op erating as a F ire Alarm S ystem wh ile in Configu ration Mod e !!
If there is no activity (no buttons pressed or switches changed) for one hour, the System will return to normal operation,
but w ill rem ain in trouble.
As
Co nfig ura tion DIP Switches
are changed to se lect diffe rent fu nction s, wa it for a fe w se con ds fo r the a ppro priate
LE D’s to change as the System rec og nize s th e cha ng e. N ote tha t Con figuratio n cha ng es tak e effe ct im m ed iate ly as
they are made; there is no
“undo”
function.
10.3 EXITING CO NFIGURATION MO DE:
To exit
Configuration Mo de
, after all desired changes are made, all Configuration DIP Switches must be returned
to a “0" o r Off po sition (b ottom pos ition). W ait about five seconds, then press the white
System Reset
button. The
System should now be back in
Normal Operation
.
10.4 FACTORY DEFAULT CONFIGURATION:
The system
as shipp ed fro m the fac tory
is configured with
no Adder Modu les
, and with certain set defaults. The
De fault settings are ...
!
All
Initiating Circuits
are
Style B (C la ss B) N on -V erifie d Ala rm s
(any Alarm on any initiating circuit activates
all indicating circuits)
!
Indicating C ircuits
are all
Co m m on Alarm
and set as
Silenceable, Temporal Code
.
!
Manual Signal Silence is
enabled
!
Two Stage
disabled
(System will operate Single Stage)
!
W ater-flow Retard Operation is
disabled
!
Au x D isc on ne ct w ill disco nn ec t co rre late d re lays
!
Auto Signal Silence Timer is
disabled
.
!
System s assu m es there are no R em ote Annun ciators
!
All Relay correlation is set to Com mon Alarm activation.
!
Fire Drill is
enabled
!
Relay Adder(s) ac tivate on Com m on Alarm
!
Signal Silence Inhibit Timer is
disabled
!
Auto General Alarm T imer is
disabled
!
System assum es there are no Adder Modules
firealarmresources.com
Содержание HCP 1000 Series
Страница 2: ...firealarmresources com...
Страница 10: ...Page 8 of 52 Fig 1A HBB 1072 Flush or Surface Enclosure Installation and Dimensions firealarmresources com...
Страница 14: ...Page 12 of 52 Fig 4 Module Mounting Locations firealarmresources com...
Страница 15: ...Page 13 of 52 Fig 4A Circuit Adder Module Mounting Details firealarmresources com...