APPENDIX "C" - MODULE SPECIFICATIONS and FEATURES
Main Fire Alarm Chassis
(HMCC1024-6[S])
General:
M
8 supervised
Style B
(Class B) or 4
Style D
(Class A)
Initiating Circuits; fully configurable. Terminals are
labelled
“INI”
. Initiating Circuits are Compatibility ID
“A”
.
Power Limited:
22 VDC, 3 mA standby, 5 mV
ripple, 50 mA max. (alarm)
M
4
Style Y or Z
(Class B or A) Indicating Circuits;
configurable as strobes or audibles. Terminals are
labelled
“IND”
.
Power Limited:
24 VDC unfiltered
1.7 A @ 49 C per Circuit
M
Up to 2
Circuit Adders
may be added.
M
Displays and Disconnect Switches
for up to
24 Circuits.
M
Optional
HPR-100 City Tie Module
.
M
Aux. Power Supply
(for Remote Annunciators).
Terminals are labelled
“AUX PWR”
.
Power Limited:
24 VDC unfiltered
1.7 A @ 49 C
M
Two
Resettable
4-Wire Smoke Supplies
. Terminals
are labelled
“4-WIRE”
.
Power Limited:
22 VDC, 200 mA each max., 300
mA total max, 5 mV ripple
M
1
RS-485 Connection
for Remote Annunciators or
interface to Audio Systems. Power Limited to 300 mA.
Terminals are labelled
“RS485”
.
M
Auxiliary relays:
(resistive loads)
Must be connected to a Listed Power Limited Source of
Supply. Terminals are labelled
“ALARM, TROUBLE,
SUPV”
.
Common Alarm:
Form C, 1 Amp, 28 VDC
Common Supv:
Form C, 1 Amp, 28 VDC
Common Trouble:
Form C, 1 Amp, 28 VDC
M
Micro-controller
Based Design.
M
Fully Configurable
from Front Panel.
M
Full
Walk-Test
function.
Electrical ratings:
M
AC Line Voltage:
102 to 132 VAC.
4 Amps. (primary)
M
Power Supply ratings:
6 Amps. max. (secondary)
M
For Indicating Circuits: 24VDC unfiltered
5 Amps. max.
M
Battery:
24VDC, Gel-Cell/Sealed Lead-Acid
Charging capability:
10-24 AH batteries
M
Current Consumption:
Standby: 200 mA, Alarm: 350 mA
Main Fire Alarm Chassis
(HMCC1024-12[S])
Same as HMCH1024-6(S) except for ...
M
Power Supply ratings:
12 Amps. max. (secondary)
M
For Indicating Circuits: 24VDC unfiltered
10 Amps. max.
M
Battery:
24VDC, Gel-Cell/Sealed Lead-Acid
Charging capability:
17-40 AH batteries
M
Current Consumption:
Standby: 200 mA, Alarm: 350 mA
Expander Chassis
(HECH1048)
M
Up to
6 Circuit Adders
may be added.
M
Displays and Disconnect Switches
for up to
48 Circuits.
M
Current Consumption:
Standby: 20 mA, Alarm: 20 mA
Digital Communicator Module
(HUDACT-100)
M
HUDACT - Digital Alarm Communicator Transmitter
using Ademco Contact ID and SIA-DCS Protocols.
45 mA,
Alarm:
120 mA
Detection Adder Module
(HDM-1008A)
M
8 supervised
Style B
(Class B) or 4
Style D
(Class A)
Initiating Circuits; fully configurable. Terminals are
labelled
“INI”
. Initiating Circuits are Compatibility ID
“A”
.
Power Limited:
22VDC, 3 mA standby, 5mV
ripple, 50 mA max. (alarm)
M
Current Consumption:
Standby:
80 mA,
Alarm:
100 mA
Signal Adder Module
(HSGM-1004A)
M
4
Style Y or Z
(Class B or A) Indicating Circuits;
configurable as strobes or audibles. Terminals are
labelled
“IND”
.
Power Limited:
24 VDC unfiltered
Max. 1.7 A @ 49C per Circuit
M
Current Consumption:
Standby:
35 mA,
Alarm:
150 mA
Relay Adder Module
(HRM-1008A)
(resistive loads)
Must be connected to a Listed Power Limited Source of
Supply. Terminals are labelled
“RLY”
.
M
8 fully Configurable
Form C Relays
.
Form C, 1 Amp., 28 VDC (resistive loads)
M
Current Consumption:
Standby:
25 mA,
Alarm:
150 mA
Polarity Reversal and City Tie Module
(HPR-100)
M
Supervised City Tie
Not Power Limited
24VDC unfiltered, 210 mA max.,
Trip coil:
14 ohms.
Terminals are labelled
“City Tie”
.
M
Polarity Reversal
Power Limited
Terminals are labelled
“Polarity Reversal”
.
24VDC open
12VDC @ 3.5 mA, 8 mA max. (shorted)
M
Current Consumption:
Standby:
35 mA,
Alarm:
300 mA
System Model:
HCP SER IES 1000
, Fire Alarm Control Panel
System Type:
Local, Auxiliary (using HPR-100), Remote Protected Premise Station (using HPR-100 or
HU DAC T-100 ), Central Station Protected P rem ises (using HU DAC T-100 ).
Type of Service:
A, M, W F, SS
Type of Signalling:
Non-Coded
Applicable Standards:
NFPA 70 and 72, UL-864, ULC S-524, ULC S-527
firealarmresources.com
Содержание HCP 1000 Series
Страница 2: ...firealarmresources com...
Страница 10: ...Page 8 of 52 Fig 1A HBB 1072 Flush or Surface Enclosure Installation and Dimensions firealarmresources com...
Страница 14: ...Page 12 of 52 Fig 4 Module Mounting Locations firealarmresources com...
Страница 15: ...Page 13 of 52 Fig 4A Circuit Adder Module Mounting Details firealarmresources com...