![Hochiki HCP 1000 Series Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/hochiki/hcp-1000-series/hcp-1000-series_installation-and-operation-manual_2143415046.webp)
Page 44 of 52
10.10 DISPLAY CONFIGURATION:
The Main and Adder Display Modules on the front panel are automatically updated to display all circuits found whenever
the function Resize - Adder Module Num ber & T ype Configuration is performed. The Main Display Module has
dedicated Trouble LEDs for the four Indicating Circuits on the M ain Fire Alarm Module. The eight Initiating Circuits (four
in Class A mode) also on the Main F ire Alarm Module are annunciated on the first column of Display Points (from top
to bottom) . Any Add er M odu le cir cuits are disp layed a fter the bas e sy stem inpu t circu its in the same order as the Adder
Modules have been installed (that is from right to left). For example, if there are two 8 Circuit Initiating Adders and one
4 Circu it Indicating Adde r, the Ma in Dis play w ill annu nciate 24 Initiating C ircuits follo wed by 4 Indic ating Circ uits. If
the Fire Alarm Control Panel is configured for Style D (Class A) Initiating Circuits, then the nu mb er of Initiating Circ uits
is cut in half, so that in the example above, there will only be a total of 12 Initiating Circuits annunciated, followed by
the 4 Adder Indicating Circuits.
Refer to the Figure shown under the Indicators, Controls, & Operation section. It shows how the first 24 Circuits are
mapped to Dis play Poi nts.
Any configured HRA 1000 Se ri es R emote A nnunc iators automatically match the main Fire Alarm Control Panel
displays, except that there will be no annunciation of Comm on Alarm, Comm on Supervisory, Battery Trouble, Ground
Fault and 4 Signal Trouble indicators.
firealarmresources.com