IMPORTANT:
The Feature
Output Circuit Correlations Enabled
must be O N for Indicating Circuit Correlations
to operate (see the Co nfigu re F eatu res sec tion), otherwise a ll Indic ating Circ uits will be
“ Co m m on Al ar m”
; they
will all activate with any
Input Circuits
configured as
Ala rm s
. Relay Circuits are always Enabled for Correlations.
Also
note tha t if the System is configured as
Two-Stage
, any
Secon d Stage / Ge neral Alarm
(cau sed by the Au to
General Alarm Timer, the General Alarm button on the Front Panel or Remote Annunciator, or by a Gen eral Alarm
Initiating Circuit) condition activates
AL L Ind ica ting C ircu its
wh ethe r they are C orre lated or no t.
10.9 CONFIGURING CIRCUIT CORR ELATIONS:
As a wo rking de finition for Co rrelation s, C ircuits c an b e de fined as ...
Input C ircuits
=
Initiating Circuits
(Detection Zone s).
Ou tput C ircuits
=
Indicating C ircuits
(Signal Zones), and
Relay C ircuits
.
W ith the Fa ctory D efault C onfigu ration, all Ou tputs are con figured to activ ate w ith any Inpu ts configured as A la rm s.
If Output Circuit Correlations are enabled (see the Configure Features section), Outputs must be configured to one
or more Inputs to activate at all. This configuration is referred to as a Correlation. There are two configuration options;
correlated indiv idua l Ou tputs to one or m ore In puts , or co rrela ting in dividua l Inpu ts to on e or m ore O utpu ts. Output
Cir cui ts may be correlated to as many Inpu t Circ uits as desired, and vice-versa.
Co rrela tion b y Inp ut C ircu it:
&
Set Config DIP Switch to 0100 0001; pause for about three seconds.
&
One and only one Inp ut C irc uit’s (Initiating Circuit / Detection Zone) Disconnect Switch is turned ON (up
positio n). This function will no t operate if more than one Input Circuit Disconnect Switch is turned ON at one
time. The se lected Input Circuit’s Yellow Trouble LED will light, as well as the Yellow Trouble LED’s of any
Output Circ uits (Indicating Circuit / Signal Zone, or Relay Circuit) that are already Correlated to that Input. If
only a check of Correlations is desired, then this is the only step required, and you may step through from one
Inpu t Circ uit to anoth er, one at a time.
&
If it is de sire d to set ne w C orre lations for the selected Input C ircuit, then the Disconnect Switch for desired
Output Circuits are turned ON (up position). The
Yellow Button
is pressed for one second; after a pause the
Yellow Tro uble LED ’s for the new ly C orre lated Ou tput C ircu its w ill be lit.
Co rrela tion b y O utpu t Circ uit:
&
Set Config DIP Switch to 0100 0010; pause for about three seconds.
&
One and only one O utp ut C irc uit’s (Indicating Circuit / Signal Zon e, or Re lay C ircuit) D isco nnec t Switch is
turned ON (up position). This function will not operate if more than one Output Circuit Disconnect Switch is
turned ON at one time. The selected Output Circuit’s Yellow Trouble LED will light, as we ll as th e Yellow
Trou ble LED ’s of any Inp ut Circ uits (Initiating Circuit / Detection Zone) that are already Correlated to that
Ou tput. If only a check of Corre lations is des ired, then this is the only step required, and you may step through
from one Ou tput C ircu it to anothe r, one at a time.
&
If it is desired to set new Correlations for the selected Ou tput Circ uit, then the Disconnect Switch for desired
Input Circuits are turned ON (up position). The
Yellow Button
is pressed for one second; after a pause the
Yellow Tro uble LED ’s for the new ly C orre lated Inpu t Circ uits w ill be lit.
At presen t, only the follow ing ty pes of Circuit CORRELATIONS are p oss ible ...
C
Alarm Circuits (Verified or not, Sprinkler or Water-flow) to Indicating Circuits or Relays.
C
Gen eral Alarm Circuits to Relay s (they are autom atically Correlated to AL L Indicating Circuits).
C
Supervisory Circuits (Latching or not) to Relays.
C
Monitor Circuits to Relays.
C
Trouble-Only Circuits to Relays
.
firealarmresources.com
Содержание HCP 1000 Series
Страница 2: ...firealarmresources com...
Страница 10: ...Page 8 of 52 Fig 1A HBB 1072 Flush or Surface Enclosure Installation and Dimensions firealarmresources com...
Страница 14: ...Page 12 of 52 Fig 4 Module Mounting Locations firealarmresources com...
Страница 15: ...Page 13 of 52 Fig 4A Circuit Adder Module Mounting Details firealarmresources com...