Fig.18:
Polarity Reversal and City Tie Module Terminal Connections
7.6 POLARITY REVERSAL and CITY TIE MODULE (MODEL: HPR-100) TERMINAL CONNECTIONS
See Appendix for Module specifications. W ire as shown using proper wire gauges.
No te tha t for us e in the US A, the installe r M UST add an A tlan tic S cie ntific (T el. 407-725-8000) Model #24544 Protective
Device, or similar
UL -Listed QV RG Sec on dary Protector
, as show n. F or use in Ca na da, the Prote ctive D evice is still
recomm ended, but the HPR-100 may be connected directly to Polarity Reversal or City Tie wiring.
Notes: 1)
Either the HPR-100’s City Tie or Polarity Reversal interface may be used, but not both.
2)
The City Tie interface is Not Power Limited.
3)
The Terminal Blocks are “removable” for ease of wiring.