2.0 GENERAL NOTES
Number of Adders that may be Installed:
Th e m axim um num ber o f Circ uit Adder M odu les tha t m ay be p hysica lly insta lled in a S ystem is ...
Main Chassis Type
HM CC1024-6(S)
or
HM CC1024-12(S)
Two
Circuit Adder Mo dules
of any type.
HM CC1024-6(S)
or
HM CC1024-12(S)
and
HECH 1048
Eigh t
Circuit Adder Mo dules
of any type.
The “S” Version Ch assis’ have Slide-Switches instead of D IP Switches for D isconnects. T he m axim um num ber of each
Circ uit Ad der M od ule
type is ...
A m axim um of 7
HDM -1008A
8 Initiating Circuit Modules (total of 64 Initiating Circuits in a system).
A m axim um of 5
HSGM -1004A
4 Indicating Circuit Mod ules (total of 24 Indicating Circuits in a system ).
A m axim um of 4
HRM -1008A
8 Relay Circuit Modules (total of 32 Relay Circuits in a system ).
MAXIMUM OF 8 ADDER MO DULES OF ANY CO MB INATION PER SYST EM.
Any HCP-1000 System m ay have a
HPR-100
or
HUDACT -100
added, and up to eight (8)
Rem ote Multiplex
Ann un ciators
externally. As good practice, it is recomm ended that Circuit Adder Modules be installed in the order
of Signals followed by Detection, followed by Relay Modules.
Circuits and Zones:
“Circuits”
refe rs to a n ac tual electrica l interfac e,
Initiating
(De tection ),
Indicating
(Signal), or
Relay
.
“Zone”
is a logical co nce pt for a Fire A larm Protecte d Area, a nd w ill consis t of at lea st on e C ircuit.
Often the terms Z one and Circuit are used interchangeably, but in this Manual the term C ircuit is used.
Display Points:
On the HCP-1000 an important concept is
Display Po ints
. Unlike som e produc ts the available LED Displays and
matching Circuit Disconnect Switches are not hard-wired to the Circuit Adder Modu les. The M ain Fire Ala rm Mod ule
and each Circuit Adder Module type have a required number of Display Points specified. In the case of Initiating
Circuits this will be reduced by half if Class “A” operation is selected. Different Main and Expander Chassis provide
a fixed number of Display Points on their attached Display Boards. These are assigned during the Configuration
Adder
Mo du le Number and Type
operation (see C onfiguration Section) as required in the cabling order in which Adder
Modules are installed. In any system setup, there must be at least as many Display Points available, as those required
by the Circuits.
Wiring Styles:
Initiating Circuits
are configured by default as Class B (Style B). They may be globally (all or none) configured as
Class A (Style D) as described in the Configuration Section. This operation uses odd and even pairs of two-wire Class
B (Style B) circu its to mak e one four-wire Class A (Style D) circuit, thus cutting in half the number of available Initiating
Circuits.
Indicating Circuits
may be individually wired as Class A (Style Z) or Class B (Style Y) without affecting the number
of circuits available (see M odule wiring instructions).
firealarmresources.com
Содержание HCP 1000 Series
Страница 2: ...firealarmresources com...
Страница 10: ...Page 8 of 52 Fig 1A HBB 1072 Flush or Surface Enclosure Installation and Dimensions firealarmresources com...
Страница 14: ...Page 12 of 52 Fig 4 Module Mounting Locations firealarmresources com...
Страница 15: ...Page 13 of 52 Fig 4A Circuit Adder Module Mounting Details firealarmresources com...