background image

Page 42 of  52

Initiating Circuits (Detection Zones)

 and 

Indicating Circuits (Signal Zones)

 are Configured by using the

Configuration DIP Switches

 to select the desired 

Circuit Type Function

, along with  the  Circu it Trouble LED’s and

Disconnect Switches. W hen a 

Circuit Type

 is selected by the 

Co nfig ura tion  DIP  Switch

 setting, the  Yellow  Troub le

LED for each  Circu it cu rre ntly configured as that type will light. To configure Circuits to be of that selected Circuit Type,
all of the desired Circuit  Disconnect Switches are turned ON (up position) and the 

Yellow Button

 is pressed for about

one second. After a short pause, the Initiating Circuit Yellow Trouble LED’s will be updated to show the new
configuration.

Note :

 Any subsequent selection of a particular Circuit as a different Circuit Type will supercede the previous selection.

Also note that the physical Circuit Type must be appropriate for the selec ted  Circu it Type; for example only Indicating
Circuits can be configured as Silenceable Strobes.

Be sure  to reset Circuit Disconnect Switches to OFF (down position) before attempting to configure any other Circuits.

CONFIG

DIP SWITCH

POSITION (1-8)

INITIATING CIRCUIT
(DETECTION ZONE)

TYPE

CONFIG

DIP SWITCH

POSITION (1-8)

INDICATING CIRCUIT

(DETECTION ZONE)

TYPE

0010 0000

Normal (Non-Verified) Alarm

0011 0000

Silenceable Audible Signal

0010 0001

Verified Alarm

0011 0001

Non-Silenceable Audible Signal

0010 0010

Sprinkler Alarm

0011 0010

Silenceable Strobe

0010 0011

Water-flow Alarm

0011 0011

Non-Silenceable Strobe

0010 0100

Non-Latching Supervisory

0010 0101

Latching Supervisory

0010 0110

General Alarm

0010 0111

Monitor

0010 1000

Trouble Only

As an example, if in a System with eight Initiating Circuits and four Indicating Circuits (Main Board only), we wanted
Class B operation,  the first six Initiating Circuits as normal Non-Verified Alarms, the last two as Latching Supervisories,
and  the las t Indica ting C ircuit as  a Non-S ilence able Strob e, the followin g se que nce  wou ld be u sed  ...

&

Restore to Default (Class B) as previously described.

&

Set Config D IP Switch  to 0010 0 000 ; all eight Initiating  Yellow  Tro uble LED ’s should light.

&

Set Config D IP Switch  to 0010 0 101 ; all eight Initiating  Yellow  Tro uble LED ’s should go o ut.

&

Set only Initiating Circuits 7 & 8 Disconnect Switches on.

&

Press the 

Yellow Button

 for on e se con d; afte r a pa use  the Ye llow T roub le LE D’s for 7 &  8 sh ould light.

&

Turn off all Disconnect Switches.

&

Set Config D IP Switch  to 0011 0 000 ; all four Indicating Ye llow T roub le LE D’s sho uld light.

&

Set Config D IP Switch  to 0011 0 011 ; all four Indicating Ye llow T roub le LE D’s sho uld go  out.

&

Set only Indicating Circuit 4 Disconnect Switch on.

&

Press the 

Yellow Button

 for on e se con d; afte r a pa use  the Ye llow T roub le LE D fo r 4 sh ould light.

&

Turn off all Disconnect Switches.

&

Exit 

Configuration Mode

.

firealarmresources.com

Содержание HCP 1000 Series

Страница 1: ...ct to change without prior notice by the manufacturer HCP 1000 SERIES Microprocessor Based Fire Alarm Control Panel INSTALLATION and OPERATION MANUAL 2000 by Hochiki America Corporation Printed Septem...

Страница 2: ...firealarmresources com...

Страница 3: ...NECTIONS Page 25 of 52 7 5 HUDACT 100 MAIN BOARD TERMINAL CONNECTIONS Page 26 of 52 7 6 POLARITY REVERSAL and CITY TIE MODULE MODEL HPR 100 TERMINAL CONNECTIONS Page 27 of 52 7 7 POWER SUPPLY CONNECTI...

Страница 4: ...S Page 16 of 52 Fig 7 Adder Display Module Page 17 of 52 Fig 8 Detection Adder Module Page 18 of 52 Fig 9 Signal Adder Module Page 18 of 52 Fig 10 Relay Adder Module Page 19 of 52 Fig 11 HUDACT 100 Di...

Страница 5: ...ith individual trouble indicators Each Circuit can be configured as Audible silenceable or Visual non silenceable Audibles may be steady Temporal Code California Code or March Time T Initiating and In...

Страница 6: ...Circuit Often the terms Zone and Circuit are used interchangeably but in this Manual the term Circuit is used Display Points On the HCP 1000 an important concept is Display Points Unlike some product...

Страница 7: ...Model HFA 1024TR Flush Trim Ring HFA 1072TR Flush Trim Ring add another suffix R for Red Enclosure Model Batteries 6 5 to 40 AH Model HMCC1024 6 6 A Main Chassis HMCC1024 12 12 A Main Chassis add Suf...

Страница 8: ...t with Disconnect Slide Switches instead of DIP Switches Model HECH1048 Expander Chassis for up to 48 additional Zones Circuits DIP Switches for Disconnect only See Module Specifications for more deta...

Страница 9: ...2 Fig 1 HBB 1024 Flush or Surface Enclosure Installation and Dimensions 4 0 MECHANICAL INSTALLATION and DIMENSIONS Install the enclosure as shown for the HBB 1024 Fig 1 or HBB 1072 Fig 1A firealarmres...

Страница 10: ...Page 8 of 52 Fig 1A HBB 1072 Flush or Surface Enclosure Installation and Dimensions firealarmresources com...

Страница 11: ...pare it for wiring the Modules Do not run the wires in between the Modules since it could cause a short circuit Use a wire tie to group wires for easy identification and neatness Be sure to connect a...

Страница 12: ...epare it for wiring the Modules Do not run the wires in between the Modules since it could cause a short circuit Use a wire tie to group wires for easy identification and neatness Be sure to connect a...

Страница 13: ...at the first module on the back tier to the right connects via HMD 575 and HMD 580 extension cables to the second module in the Main Chassis and the fourth module on the front tier to the right connec...

Страница 14: ...Page 12 of 52 Fig 4 Module Mounting Locations firealarmresources com...

Страница 15: ...Page 13 of 52 Fig 4A Circuit Adder Module Mounting Details firealarmresources com...

Страница 16: ...talled P1 RS 485 Connection for future expansion P2 Connector for HPR 100 Module or HUDACT 100 P3 Connector for Display Module part of HMCH 1024 P4 Connector for future expansion P5 Connector for Circ...

Страница 17: ...nts Chassis Type Display Points There are also 4 Display Points dedicated to the 4 Main Board Indicating Circuits HMCC1024 6 24 The first 8 or 4 of these depending upon Style B or D operation are dedi...

Страница 18: ...Fig 6A Main Display Module HMCC1024 6S HMCC1024 12S Chassis for the USA Market only the Main Display Module appears as shown below The Disconnect DIP Switches are replaced by Slide Switches firealarm...

Страница 19: ...figuration Operation sections of Manual The Adder Display Module provides the following general purpose Display Points Chassis Type Display Points HECH1048 48 Note that the Adder Display Module comes...

Страница 20: ...s A Style D operation of Initiating Circuits 7 and 8 JW5Continuity Jumper removed if there are any more Adder Modules installed Jumper JW6 on the Main Fire Alarm Module must be removed if there are an...

Страница 21: ...d The HRM 1008A requires 8 Display Points 6 7 HUDACT DIGITAL COMM UNICATOR MODULE Model HUDACT 100 P1 Cable to P8 on the Main Fire Alarm Board P2 RS 485 Connection for future expansion P3 Not used P4...

Страница 22: ...em trouble occurs the designated terminals will transmit a zero volts or open circuit Please note that at normal condition the terminals polarity is read exactly as labelled on the circuit board Jumpe...

Страница 23: ...See wiring tables and Appendix A for compatible devices and Appendix C for specifications Caution Do not exceed power supply ratings Main Chassis HMCC1024 6 S total current for Indicating Circuits is...

Страница 24: ...Page 22 of 52 Fig 14 Main Fire Alarm Module Terminal Connections continued Note All Initiating Circuits are Compatibility ID A firealarmresources com...

Страница 25: ...008A TERMINAL CONNECTIONS Wire devices to terminals as shown See wiring tables and appendix A for compatible devices See appendix C for Module specifications Note The Terminal Blocks are removable for...

Страница 26: ...SIGNAL MODULE HSGM 1004A TERMINAL CONNECTIONS Wire devices to terminals as shown See wiring tables and appendix A for compatible devices See appendix C for Module specifications Note The Terminal Blo...

Страница 27: ...RELAY MODULE HRM 1008A TERMINAL CONNECTIONS Wire devices to terminals as shown See wiring tables and appendix A for compatible devices See appendix C for Module specifications Note The Terminal Block...

Страница 28: ...uired RJ31X Connector Line 1 Output Tip Ring To an optional Premise Telephone on the first Telephone Line via the required RJ31X Connector Line 2 Input Tip Ring To the second Telephone Line via the re...

Страница 29: ...an Atlantic Scientific Tel 407 725 8000 Model 24544 Protective Device or similar UL Listed QVRG Secondary Protector as shown For use in Canada the Protective Device is still recommended but the HPR 1...

Страница 30: ...y total current 6 A maximum Battery Fuse on Main Module Replace with 20 Amp 1 1 4 Fast Acting Fuse Model HMCC1024 12 S Main Chassis Electrical input ratings 120 VAC 60 Hz 4 A main primary circuit brea...

Страница 31: ...m Ohms 0 06 2350 716 3750 1143 6000 1829 8500 2591 30 0 12 1180 360 1850 567 3000 915 4250 1296 15 0 30 470 143 750 229 1200 366 1900 579 6 0 60 235 71 375 114 600 183 850 259 3 0 90 156 47 250 76 400...

Страница 32: ...ccurs its designated trouble indicator will be illuminated as well as the comm on trouble indicator and trouble buzzer To correct the fault check for open wiring on that particular Circuit loop or if...

Страница 33: ...rcuit Circuit Indicators and Disconnect Switches LED Indicators may be Amber Red or Green and may illuminate continuously steady or at one of two Flash Rates Fast Flash 120 flashes per minute 50 duty...

Страница 34: ...ill is active Acknowledge LED If the Panel is configured as Two Stage the Acknowledge Indicator flashes amber at the Fast Flash Rate while the Auto General Alarm Timer is timing out It turns on steady...

Страница 35: ...s activated Buzzer Silence Button Blue Activation of the Buzzer Silence button while the Buzzer is sounding silences the Buzzer The Buzzer will resound if there is a subsequent event Pressing the butt...

Страница 36: ...larm Sprinkler Alarm General Alarm and Latching Supervisory does not affect its status until the Panel is reset Disconnecting an active Non Latching Initiating Circuit including Non Latching Superviso...

Страница 37: ...m Timer if configured starts and the Acknowledge Indicator starts flashing Subsequent First Stage alarms when the Panel is already in Alarm cause the following The Buzzer sounds steadily If Signals ha...

Страница 38: ...Retardmay not exceed 120 seconds General Alarm To provide Remote General Alarm such as for remoted key switches In a Two Stage System these inputs perform exactly the same function as the Front Panel...

Страница 39: ...urning them all OFF put switches in the bottom or OFF positions then performing a SYSTEM RESET WHILE IN CONFIGURATION MODE THE FIRE ALARM CONTROL PANEL IS NOT OPERATING Three buttons and LED indicator...

Страница 40: ...er 0000 1101 0D Yellow Evacuation Code Selection 0000 1110 0E Yellow Number of Remote Annunciators 0010 0000 20 Yellow Normal Non Verified Alarm INITIATING CIRCUITS DETECTION ZONES 0010 0001 21 Yellow...

Страница 41: ...desired changes are made all Configuration DIP Switches must be returned to a 0 or Off position bottom position W ait about five seconds then press the white System Reset button The System should now...

Страница 42: ...xited if the Default Settings are acceptable 10 6 RESIZE SYSTEM SET CIRCUIT ADDER MODULE NUMBER TYPE Resizing the System without performing a full Restore to Defaults may be done if the only change is...

Страница 43: ...ny set Correlations see Correlation section If the Yellow LED is not lit all Output Circuits are Common Alarm all outputs turn on for any Alarm Input 0000 0111 Waterflow Sprinkler Retard Operation Yel...

Страница 44: ...enceable Audible Signal 0010 0001 Verified Alarm 0011 0001 Non Silenceable Audible Signal 0010 0010 Sprinkler Alarm 0011 0010 Silenceable Strobe 0010 0011 Water flow Alarm 0011 0011 Non Silenceable St...

Страница 45: ...uble LED will light as well as the Yellow Trouble LED s of any Output Circuits Indicating Circuit Signal Zone or Relay Circuit that are already Correlated to that Input If only a check of Correlations...

Страница 46: ...r example if there are two 8 Circuit Initiating Adders and one 4 Circuit Indicating Adder the Main Display will annunciate 24 Initiating Circuits followed by 4 Indicating Circuits If the Fire Alarm Co...

Страница 47: ...f Circuits that may be set at any one time for Walk Test is 15 The burst interval is half a second on half a second off After the sounding pattern has been sent on the Indicating Circuits the Initiati...

Страница 48: ...03 PSD 7130 70 201000 003 SIJ 24 NS4 220 6270C 003 PSD 7130 70 201000 005 SIJ 24 HSC 220R PSD 7128 70 201000 001 SLR 24 NS6 220 CERBERUS PYROTRONICS PSD 7126 70 201000 002 SLR 24 NS4 220 D1 2 PSD 7126...

Страница 49: ...1 B406B A A 0 12 mA SLR 24 NS6 220 HD 3 HB 3 0 045mA SLR 24 NS4 220 HD 3 HB 3 0 045mA SENTROL ESL SLR 24H NS6 220 HD 3 HB 3 0 045mA 429C S10A N A 0 10 mA SLR 24H NS4 220 HD 3 HB 3 0 045mA 429CT S10A N...

Страница 50: ...S241575 S241575W S2475 S2475W S24110 S24110W H12 24 H12 24W MDL MDLW Wheelock AS 2415W 24 FR AS 241575W FR AS 2430W FR AS 2475W FR AS 24110W FR AS 2415C FW AS 2430C FW AS 2475C FW AS 24100C FW AH 24...

Страница 51: ...Common Indicators and Controls and 32 Circuit Capacity HRAX 1048 Adder Annunciator Chassis with 48 Circuit Capacity HRAM 1016 Non Expandable Annunciator Chassis with Common Indicators and Controls an...

Страница 52: ...its 24VDC unfiltered 10 Amps max M Battery 24VDC Gel Cell Sealed Lead Acid Charging capability 17 40 AH batteries M Current Consumption Standby 200 mA Alarm 350 mA Expander Chassis HECH1048 M Up to 6...

Страница 53: ...g Circuit Module X 0 035 0 150 HRM 1008A 8 Relay Circuit Module X 0 025 0 150 HUDACT 100 Digital Communicator Module X 0 045 0 120 HPR 100 City Tie Module X 0 035 0 300 2 Wire Smoke Detectors X 0 0001...

Страница 54: ...ible to repair or replace equipment which has been repaired by others abused improperly installed altered or otherwise misused or damaged in any way Unless previously contracted byHochiki Hochiki will...

Отзывы: