71
F1 GROUP
:
Motor Parameter
(
total 11 items
)
Code
Name
Setting Scope
Min Unit
Defaulted
Value
Addre
ss
Change
F1.05
Stator resistance
0.0
~
50.00%
0.01%
Power
determinati
on
105H
○
F1.06
Leakage inductance
0.0
~
50.00%
0.01%
Power
determinati
on
106H
○
F1.07
Rotor resistance
0.0
~
50.00%
0.01%
Power
determinati
on
107H
○
F1.08
Mutual inductance
0.0
~
2000.00%
0.1%
Power
determinati
on
108H
○
F1.09
Rated slip frequency
0.00
~
20.00Hz
0.01Hz
0Hz
109H
○
F1.10
Auto tuning
0: Auto tuning disable
1: Stationary auto tuning
2: Rotating auto tuning
1
0
10AH
×
F2 Group
:
Start/Stop Parameter
(
Total 15 items
)
Code
Name
Setting Scope
Min Unit
Defaulted
Value
Addre
ss
Change
F2.00
Reserved
-
-
-
200H
*
F2.01
Start frequency
0.20
~
60.00Hz
0.01Hz
0.5Hz
201H
○
F2.02
Start frequency hold time
0.0
~
10.0s
0.1s
0.0s
202H
○
F2.03~
F2.07
Reserved
-
-
-
203H
~
207H
*
F2.08
Stop modes
0
:
Decelerate to stop
1
:
Coast to stop
2
:
Deceleration + DC
braking
1
0
208H
×
F2.09
Frequency threshold of DC
braking
0.00
~
60.00Hz
0.01Hz
1.00Hz
209H
○
F2.10
DC brake delay time
0.00
~
10.00s
0.01s
0.00s
20AH
○
F2.11
DC Brake current
0.0
~
150.0% Inverter rated
current
0.1%
120.0%
20BH
○
F2.12
DC Brake time at stop
0.0s No action
;
0.1
~
60.0s Action
0.1s
0.5s
20CH
○
F2.13
Dynamic braking
0
:
Disabled
1
:
Enable
1
0
20DH
×
F2.14
Reserved
-
-
-
20EH
*
Содержание HV950-1R5G1(B)