56
Figure 6-76 Stall Overvoltage
FL.04~ FL.06 Reserved
Reserved
FL.07 Auto current limiting
threshold
Range
:
20~200%
【
160%
】
FL.08 Reserved
Reserved
FL.09 Action mode of auto
current limiting
Range
:
0
~
5
【
5
】
Auto current limiting function is used to limit the load current under the preset
current in real time to avoid trip due to over-current. This function is
especially useful for the applications of larger load inertia or sharp change of
load.
FL.07 defines the threshold for current limiting. Its setting is a percentage of
inverter’s rated current.
The action mode of auto current limiting function is decided by FL.09.
FL.09
=
0: When running in constant speed, auto current limit is invalid
FL.09
=
1: When running in constant speed, auto current limit is valid
FL.09
=
2: Auto current limit is valid all the time (mode 1)
FL.09
=
3: Reserved
FL.09
=
4: Reserved
FL.09
=
5: Auto current limit is valid all the time (mode 2)
Because the output frequency might change during current limiting, the
function should be used for applications that require constant speed and stable
frequency output.
FL.10~ FL.13 Reserved
Reserved
FL.14 Fault type of the first two
times
Range
:
0
~
29
【
0
】
FL.15 Fault type of the previous time Range
:
0
~
29
【
0
】
FL.16 Fault type of the last time
Range
:
0
~
29
【
0
】
Stall
overvoltage
point
Output
freq.
Time
Time