91
0x3308
Output Power
0x3309
Running RPM
0x330A
Reserved
0x330B
Analog closed-loop feedback
0x330C
Busbar voltage
0x330D
External counter
0x330E
Output torque
0x330F
Switch input and output terminals status
:
BIT0~15=X1~X5,
NC,NC,NC,Y1, NC, TC,NC, FAN, BRAKE, NC, NC
0x3310
Preserve
0x3311
Operation frequency after compensation
0x3312
The first run failure
0x3313
The second run failure
0x3314
The third( last time) run failure
0x3315
Operation frequency setting
0x3316
Running speed setting
0x3317
Analog closed-loop given
0x3318
Reserved
0x3319
Reserved
0x331A
AI
0x331B
Reserved
0x331C
Set acceleration time 1
0x331D
Set deceleration time 1
0x331E
Command given channel
:
0
:
Panel control
1
:
Terminal control
2
:
Serial port control
0x331F
Inverter status word 2
0x3320
Frequency given channel
:
0
:
Digit given 1
,
Keypad
∧∨
adjustment
1
:
Digit given 2
:
Terminal UP/DN adjustment
2
:
Digit given 3
:
Serial port
3
:
Reserved
4
:
AI Analog given
5
:
Reserved
Inverter control word bits are defined as follows
:
Control word
(
bit
)
Value
Function
Description
Bit2
、
1
、
0
111B
Run Command
Start the inverter
110B
Mode 0 stop
Stop according to
setting deceleration
time
101B
Mode 1 stop
Free stop
011B
Mode 2 stop
Reserved
100B
External fault stop
Freestop,Inverter
display external fault
Rest
No command
Bit3
1
Reverse
Run setup effective
operation direction
(Inching mode is
invalid)
0
Forward
Bit4
1
Inching
to
run
froward
Содержание HV950-1R5G1(B)
Страница 1: ...1 HV950 Series Small Power Frequency Inverter User Manual HNC Electric Limited ...
Страница 95: ...95 ...