4 HANDLING
4-31
4.7 Handling Scan-type Analog Input Modules
4.7.1 Mounting
modules
Use the A/D conversion module and scanner modules in the combinations listed below. They
cannot be installed in a CPU unit mount base or I/O unit mount base.
Slot number
→
0 1 2 3 4 5 6
7
PS
ST
AD
S
canner
S
canner
S
canner
S
canner
S
canner
S
canner
S
canner
z
Mount the A/D conversion module in I/O slot 0. It cannot be mounted in I/O slots 1 to 7.
z
Up to seven scanner modules can be installed in I/O slots 1 to 7. Mount them in these
slots from the leftmost position.
z
Other I/O modules can be installed in I/O slots 1 to 7 as well. When they are installed
concurrently with the A/D conversion module and scanner modules, however, they cannot
intervene between the A/D conversion module (I/O slot 0) and scanner modules. Install
them in the slots to the right of the scanner modules
.
<Correct> <Incorrect>
PS ST AD
S
canner
S
canner
S
canner
S
tandard I/O
S
tandard I/O
S
tandard I/O
S
tandard I/O
PS ST AD
S
tandard I/O
S
canner
S
canner
S
tandard I/O
S
canner
S
tandard I/O
S
tandard I/O
4.7.2 Wiring
modules
Follow the instructions in Section 4.2, “Wiring I/O Modules,” to wire modules.
4.7.3 Usage
Scan-type analog input modules enter analog data into the EW area. To perform input into
the EW area, the input and output addresses and the module type must be registered by using a
programming tool. To find out more on registering such information, refer to one of the
manuals named below. When registering the module type, register it as LQA000.
Manual name
Manual number
S10 Tools For Windows® V7
SAE-3-120
LADDER CHART For Windows®
SAE-3-121
4-CHANNEL ANALOG PULSE COUNTER For Windows®
SAE-3-142
Description
Separately
insulated
Commonly insulated
PS
LQV000 or LQV020 or LQV100
ST
LQS000
LQS000 or LQS020
AD LQA301
LQA800
Scanner LQA310 LQA810
Содержание S10mini LQS070
Страница 1: ......
Страница 2: ......
Страница 19: ...This Page Intentionally Left Blank ...
Страница 30: ...1 BEFORE USE ...
Страница 37: ...This Page Intentionally Left Blank ...
Страница 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Страница 57: ...This Page Intentionally Left Blank ...
Страница 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Страница 143: ...This Page Intentionally Left Blank ...
Страница 144: ...4 HANDLING ...
Страница 179: ...This Page Intentionally Left Blank ...
Страница 180: ...5 HANDLING I O DATA ON J NET ...
Страница 186: ...6 HANDLING I O DATA ON D Station ...
Страница 191: ...This Page Intentionally Left Blank ...
Страница 192: ...7 MAINTENANCE ...