3 INDIVIDUAL SPECIFICATIONS
3-53
A/D
SV0
SC0
SV7
SC7
LQA055 internal circuit
Class D grounding
Class D grounding
Amplifier
8-channel
External terminal block
CAUTION
Wire the cable shield to the external terminal block and use Class D grounding
collectively.
Figure 3-68 LQA055 Circuit
+5
+5.12
0
-5
-5.12
(8,191)2,047
(8,000)2,000
-2,000(-8,000)
-2,048(-8,192)
+5
+5.09
(8,191)2,047
(8,000)2,000
0
+1
+10
+10.24
0
-10
-10.24
(8,191)2,047
(8,000)2,000
-2,000(-8,000)
-2,048(-8,192)
Input voltage [V]
A/D conversion data [digit]
Given
±
5 V inputs:
Given
±
10 V inputs:
(Note) Each number in parentheses is the result
of a 14-bit conversion.
A/D conversion data [digit]
Input voltage [V]
Input voltage [V]
A/D conversion data [digit]
Given 1 to 5 V inputs:
Figure 3-69 LQA055 A/D Conversion Characteristics