4.3.5 Circuit protection fuses
Install fuses as described below to minimize the burnout and damage to I/O modules,
attachments and connections.
Table 4-1 I/O Module Fuse Ratings
Module type
Fuse rated
breaking current
Fuse location
LQY100 10
A
Install one fuse per common. Install one on the positive
side of a DC load, or on both sides of an AC load.
LQY140
LQY150
LQY160
LQY170
5 A
Install one fuse per point. Install one on the positive side
of a DC load, or on both sides of an AC load.
LQY200 5
A
Install one fuse per common. Install one on the positive
side of a 24 VDC power supply.
LQY300
LQY310
3 A
Install one fuse per common. Install one on the positive
side of a 24 VDC power supply.
LQY350
LQY360
3 A
Install one fuse per common. Install one on the positive
side of a 24 VDC power supply.
LQZ300 3
A
Install one fuse per common. Install one on the positive
side of a 24 VDC power supply.
CAUTION
Install a protective circuit, such as a fuse or circuit protector, in the external
power supply. The protective circuit must be one matched to the rating of the
power supply.
Содержание S10mini LQS070
Страница 1: ......
Страница 2: ......
Страница 19: ...This Page Intentionally Left Blank ...
Страница 30: ...1 BEFORE USE ...
Страница 37: ...This Page Intentionally Left Blank ...
Страница 38: ...2 KINDS AND SPECIFICATIONS OF I O MODULES ...
Страница 57: ...This Page Intentionally Left Blank ...
Страница 58: ...3 INDIVIDUAL SPECIFICATIONS ...
Страница 143: ...This Page Intentionally Left Blank ...
Страница 144: ...4 HANDLING ...
Страница 179: ...This Page Intentionally Left Blank ...
Страница 180: ...5 HANDLING I O DATA ON J NET ...
Страница 186: ...6 HANDLING I O DATA ON D Station ...
Страница 191: ...This Page Intentionally Left Blank ...
Страница 192: ...7 MAINTENANCE ...