3. Servicing
Cycle components
SMGB0097 rev.0 - 07/2015
69
3
2
Remove the 2 Victaluic connections from the
water connections.
Victaulic
connections
3
Screw eyebolts to both sides of the cooler to the
bolts for that purpose. Fasten a textile belt to
proceed to lift the cooler.
C A U T I O N
Do not never use chains or metallic ropes to lift the
cooler as they can damage it.
4
Unscrew the 4 screw of the foot plate heat
exchanger.
2 Screws
2 Screws
5
Remove de cooler. Softly lift the cooler and
place it on a strong and stable surface.
C A U T I O N
In spite of water shut-off valves are closed,
water inside the plate heat exchanger and
water pipe remain.
C A U T I O N
Plate heat exchanger is heavy, two persons
and a portable crane or similar are required.