4. Troubleshooting
Troubleshooting by alarm code
SMGB0097 rev.0 - 07/2015
114
Alarm code
01-01
Startup Circuit Failure
Alarm stop reason
Startup circuit fails to self-hold after reception of operation signal, or upon automatic recovery from instant power failure.
PCB monitoring position
PCBc (CPU PCB) PCN15,PCN17
Revision of connections
Revision of connections
Revision of connections
Replace relay XR
Yes
Yes
Yes
No
No
No
The connection and insertion of connector
PCN15 on PCBc (CPU PCB) is correct
The connection and insertion of connector
PCN17 on PCBc (CPU PCB) is correct
The insertion of the terminal of relay XR is
correct
Alarm code
05-05
Reverse/Open Phase
Alarm stop reason
Power source connected locally is connected in reverse or in open phase.
PCB monitoring position
PCBd (I/O PCB) 3-phase support R, S, T
Inspect power source and
voltage
Manual correction of
connection and insertion
Revision of wiring
Check PCBd (I/O PCB)
No
Yes
Yes
Yes (Open reverse phase)
No
No
3-phase power source shows open or reverse
phase
The connection and insertion of the
connector of 3-phase connectors R,S,T to PCBd
(I/O PCB) is correct
Power source of R,S,T connector shows
open or reverse phase