4. Troubleshooting
Troubleshooting by alarm code
SMGB0097 rev.0 - 07/2015
109
4
Alarm code
C1-26
Suction Gas THM Abnormality (CN27)
Alarm stop reason
Thermistor for detection of temperature of gas suctioned (Ts) by compressor indicates an abnormal value.
PCB monitoring position
PCBd (I/O PCB) CN27
N O T E
Refer thermistor characteristics chapter.
Replace thermistor
Correction of connections
Replace PCB
d
(I/O PCB)
The connection and
insertion of connector
CN27 on PCB
d
(I/O PCB)
are correct
Yes
Yes
No
No
Remove the
connectors and
measure thermistor resistance.
Is resistance value
normal?