![Hitachi 8E042340 Скачать руководство пользователя страница 51](http://html.mh-extra.com/html/hitachi/8e042340/8e042340_service-manual_140450051.webp)
2. Control Functions
Control of Master/Slave group
SMGB0097 rev.0 - 07/2015
44
5
Remote Forced Stop (Alarm Reset) / System Recovery Wiring
Connect to each chiller unit to force stop of a chiller unit in operation from a remote location, to reset an alarm, or to
return to the system a chiller unit that had been excluded from the target of the control of Master/Slave group. (When a
chiller unit is stopped because of an alarm, or by a forced stop order, it becomes excluded from the target of the control
of Master/Slave group (detached). It is necessary to perform system recovery operation in order to regain the target of
the control of Master/Slave group.
Also, in case of using it to reset an alarm, it is necessary to enable the optional function (LCD screen setting) "Remote
stop reset" at each of the chiller units.
5<
5<
(Forced stop signal)
(Alarm reset)
(System recovery
signal)
Remove the connection
between 5 and 6
5<
5<
System recovery signal
Forced stop-Alarm reset
signal
5<
More than 200ms
ON
OFF
Alarm
Output
ON
OFF
Alarm reset
5<
More than 200ms
ON
OFF
Run
Stop
Relevant
Unit
Forced stop
5<
More than 200ms
ON
OFF
Detached
from
control
target
Relevant
Unit
System recovery
N O T E
• It is also possible to perform forced stop by the push button switch (Stop) and to perform system recovery by the push
button switch (Run) in the module.
• Led RL
2
on: on order
• Led RL
2
off: off order