4. Troubleshooting
Troubleshooting by alarm code
SMGB0097 rev.0 - 07/2015
100
Alarm code
C1-51
Compressor overcurrent
Alarm stop reason
The running current for one compressor is increased above the value for activation of the overcurrent relay, thus activating
the (thermal) overcurrent relay.
PCB monitoring position
PCBd (I/O PCB) PCN206
Check of PCB
d
(I/O PCB)
Press the reset button of
the overcurrent relay
Check of wiring
(disconnection)
Check of overcurrent relay
(internal disconnection)
Power source voltage too high or too low
Phase unbalance of the power source
voltage
Lock status of compressor motor
Power source fuse
Loosening of screws of power source
terminal
Inspection of electromagnetic switches
(single phase operation)
Decrease of insulation of compressor motor
Malfunction of slide valve of compressor
I/O PCB is normal
Check of PCB
d
(I/O PCB)
Overcurrent relay
(51C1) is activated
Yes
No
Overcurrent relay
(51C1) is being reset
Yes
No
Yes
No
Remove the
wiring inserted into
connector PCN206 on
PCB
d
(I/O PCB) and mesure
conductivity. Is there
conductivity?
Operation control
results in immediate
activation of alarm
Yes
No