2. Control Functions
Control functions on the module
SMGB0097 rev.0 - 07/2015
15
2
2.1.4 Control for recovery from power interruption (Option)
When this function is enabled, even in the case of power interruptions exceeding 2 seconds in length, operation
restarts automatically in the operation mode as before the power failure, once a 3-minute guard has passed.
To enable this function, the DIP switch of option C on the settings PCB (PCB
A
) (DSW5-1#) has to be set to ON.
Setting PCB (PCBA)
1 2 3 4
DSW5
ON
ON
Option C
Momentary power failure where rated
voltage drops by more than 20% with a
duration between 12ms and 2s
When the function for recovery
from power failure is selected
(In case that this function is
not selected, it is necessary to
restart operation)
Power failure exceeding 2
seconds
Power source
status
ON
OFF
ON
OFF
ON
OFF
ON
OFF
Pump operation
order
Chiller unit
operation status
Compressor
operation status
min
min
Time guard
Time guard
Selected from DIP
switches
N O T E
• When this function is enabled, recovery upon restoration of the power supply returns to the state before the power
interruption. In case that the chiller unit was in operation before the power interruption, it restarts upon recovery of the
power source. Depending on the situation, this may lead to unintentional automatic startup of the chiller unit.
• The control for recovery from power interruption restarts in the same state as before the occurrence of the power
interruption. Therefore, in case that the power interruption occurs while the unit is stopped, it remains stopped even
upon recovery of the power source.