4. Troubleshooting
Troubleshooting by alarm code
SMGB0097 rev.0 - 07/2015
103
4
Alarm code
C1-91
Cooler Inlet Decrease
Alarm stop reason
Inlet refrigerant temperature of the heat exchanger (Te) becomes lower than -6.5ºC for more than 3 seconds. (only enabled
in cooling).
N O T E
Causes alarm stop with 3 occurrences in 30 minutes. Retry control is performed until the second one. (Compressor
stops, and restarts automatically after 3 minutes)
Inlet refrigerant temperature of the heat exchanger (Tr) becomes lower than -35ºC for more than 10 seconds. (only enabled
in defrosting)
N O T E
Retry is not performed during during defrosting.
Retry indication
LCD: By touching “Inspection”, “Cooler Inlet Retry” is shown in “No.1 Cycle”.
Retry code
C1-P6
PCB monitoring position
PCBd (I/O PCB) CN29 (Cooler inlet thermistor)
Lack of refrigerant. Gas leakage
Malfunction of check valve
Clogging of water strainer
Clogging of low pressure side pipes
Adjustment of cold water thermo settings.
Shall be within usage range
Malfunction of expansion valve
Adjustment of reverse rotation of pump
Clogging of expansion valve
Adjustment of water quantity (adjustment
of inlet-outlet water temperature)
Replace thermistor
Correction of
connections
Check of PCB
d
(I/O PCB)
The connection and
insertion of connector
CN29 on PCB
d
(I/O PCB)
are correct
Yes
Yes (There are problems)
No (There are no problems)
Yes
No
No
Cooler inlet
refrigerant temperature
has actually dropped to the
activation value
There are
problems with thermistor
characteristics