Figure 2-2 System Wiring Diagram (General Wiring)
Note
●
The supplied interconnecting cable length is 5.5 m.
●
The suggested inner diameter of the low voltage conduit is larger than 30 mm.
●
If you want to bury both of the AC power cord and the low voltage cable at the entrance, the
two cables should be in separated conduits to avoid interference.
●
If more peripherals are required to connect, you should increase the conduit diameter or bury
another conduit for the external cables.
●
The external AC power cord should be double-insulated.
●
The network cable must be CAT5e or the network cable has better performance. And the
suggested network cable length should be less than 100 m.
DS-K3B802X Series Swing Barrier User Manual