Note
• Up to 80 bits are allowed in the total length.
• The odd parity start bit, the odd parity length, the even parity start bit and the even parity
length range from 1 to 80 bit.
• The start bit of the card ID, the manufacturer code, the site code, and the OEM should range
from 1 to 80 bit.
6. Set output transformation rule.
1) Click Set Rule to open the Set Output Transformation Rules window.
Figure 6-7 Set Output Transformation Rule
2) Select rules on the left list.
The selected rules will be added to the right list.
3) Optional: Drag the rules to change the rule order.
4) Click OK.
5) In the Custom Wiegand tab, set the rule's start bit, length, and the decimal digit.
7. Click Save.
6.7.5 Configure Card Reader Authentication Mode and Schedule
You can set the passing rules for the card reader of the access control device according to your
actual needs.
DS-K3B501S Series Swing Barrier User Manual
69