Chapter 4 – Ways to Set Scale Parameters
Hardy Process Solutions HI 6200 Weigh Processor User Guide
35
4.3 Using a PLC
4.3.1 EIP
Many of the set-up procedures in this section require an EIP system. In this section, the
Allen Bradley system is used.
Note:
The HI 6200 is not compatible with the obsolete HI 215IT Junction Boxes.
Make sure the HI 6200 is installed with the HI6020IT, HI 6020JB, HI 6010IT or HI
6010JB Junction Boxes. It is compatible with the HI 215JB without the IT functions.
4.3.2 Setting Up Communications
The following procedure describes how to set up communications between the ControlLogix
PLC and the HI 6200. This procedure requires a new or open RS Logix® 5000 project. For
instructions, see your RS LOGIX 5000 manual.
For this setup example/instructions, use the
EDS_AOP
file. This file is available as a free
download from the
Hardy website
. For information about how to install EDS files, see the
Rockwell instructions.
1. In the program Controller Organizer, find the
I/O Configuration
section.
2. Right-click the Ethernet Module under which you will be installing the HI6200-WS module.
3. Select
New Module
to display a list of modules.
4. From the catalog list, select the Hi6200 Series EDS_AOP module.