72
D REGISTER
Description
0604
HYS
Dead band (Hysteresis (ON/OFF control))
G.OUT
0605
HEO
Heat Emergency Output
G.OUT
0606
CEO
Cool Emergency Output
G.OUT
0607
OL-H
Output high limit
G.OUT
0608
OL-L
Output low limit
G.OUT
0610
INP
Input type selection
G.IN
0611
UNIT
Input range unit selection
G.IN
0612
FR-H
Upper range
G.IN
0613
FR-L
Lower range
G.IN
0614
DP-P
Decimal point input
G.IN
0615
SL-H
High scale
G.IN
0616
SL-L
Low scale
G.IN
0617
FILT
PV bias
G.IN
0618
BIAS
PV bias
G.IN
0619
B.OUT
Show PV during input (sensor) disconnection
G.IN
0620
RJC
RJC ON/OFF
G.IN
0621
U.UNIT
User unit selection
G.IN
0700
CPTNO_S
Pattern number to edit or pattern number source to copy
0701
CPTNO_D
Pattern number destination to copy
0702
CSEGNO
Segment number to edit
0703
CFCMD
Edit command [see below]
0704
CFANS
Edit result [see below]
0800~0840
SEG value to edit (see program parameter)
0900
TUPT
Total number of used patterns
0901~0930
NPTx
Quantity of used segment in each pattern (X is the symbol that represents the pattern number)
0931
TUSEG
Total number of used segments
1001~1099
MSVxx
SV per each segment of the running pattern (xx is the symbol that represents the segment number)
1101~1199
MTMxx
TM per each segment of the running pattern (xx is the symbol that represents the segment number)
Value
command
Description
1
INIT
D0700~D0704 Init
2
FREAD
After reading the CSEGNO of the CPTNO_S display it under the D0800
3
FWRITE
Write the content under the D0800 in the CSEGN of the CPTNO_S
4
CPYPTF
Copy the PT content of the CPTNO_S into the PT of the CPTNO_D
5
DELPTF
Delete the PT of the CPTNO_S
6
INSSEG
Insert in the CSEGNO of the CPTNO_S
7
DELSEG
Delete the CSEGNO content of the CPTNO_S
8
PTUPLOAD
After uploading the PT content of the CPTNO_S, show under the D1000
Value
command
Description
1
DONE
Execution OK
2
NO PT
No corresponding pattern (No SEG or Range Out)
3
NO SEG
No corresponding pattern (No SEG content or Range Out)
4
PT RUN
Correspondent Pattern running
5
PAR ERR
Other command error
●
[see] CFCMD (D0703) : Edit command
●
[see] CFANS (D0704) : CFANS result
Содержание NP200