66
◼
Function
Measuring
Input
Bias
-100.0 ~ 100.0% for measuring input range.
Valid setting a correction value
Scaling
According to setting of SL-H, SL-L of measuring range, scaling is available.
Input filter
OFF, 1 ~ 120 s
Control
Fix SV
4 kinds
Pattern
30 Patterns, 99 segments are available in each pattern
Segment
300 Segments
PID Group
4 kinds
Auto Tuning
According to SV, AT is operating.
(Select STD or low PV)
Proportional band (P)
0.1% ~ 999.9%
Integral time (I)
OFF, 1 ~ 6000sec
Differential time (D)
OFF, 1 ~ 6000sec
ON/OFF control
Select ON/OFF control in output group
PID converter
Level PID/Segment PID selectable
Manual reset
-0.5 ~ 105.0%. 〔Valid when I=OFF〕
Direct/reverse action
Select direct or reverse action in output group
Emergency output
-0.5 ~ 105.0% of output value
ON/OFF hysteresis
0.0 ~ 100.0% of range (in case of ON/OFF control, it is up to hysteresis value in output group.)
Heating/cooling hysteresis
-100.0 ~ 50.0% of output value
Auto/Man
Convert at the 5th operation screen
Anti reset wind up (ARW)
AUTO, 50.0 ~ 200.0% at the PID group
Retransmission
output
Retransmission signal
PV, SV, MV, SPS (select TRANS in retransmission group)
Scaling
Setting PV, SV
Alarm
Setting points
Max 10 points
Type of alarm
High/low alarm, High/low deviation alarm
Setting range
Process alarm: 0~100% of range
Deviation alarm: -100~100% of range
Alarm hysteresis
0.0~100.0% of instrument range
◼
Condition for transportation & storage
◼
Structure
Temperature
–25 ~ 70 ℃
Humidity
5 ~ 95 %RH (no icing)
Shock
Fall from less than 1m
Material
Plastic case
Weight
696 g (including bracket and box)
Panel cutout
92(W) X 92(H)