22
Menu
Code
Parameter
Setting Range
Display Condition
Default
Value
G.QUICK
USE
Quick menu use or not
OFF / ON
Always
OFF
G.PRG
PRG Group use or not
ON
G.FILE
FILE Group use or not
G.AT
AT Group use or not
G.PID
PID Group use or not
G.SV
SV Group use or not
G.CTRL
CTRL Group use or not
G.IS
IS Group use or not
G.ALARM
ALARM Group use or not
G.UO
UO Group use or not
G.TRANS
TRANS Group use or not
G.COMM
COMM Group use or not
G.OUT
OUT Group use or not
G.IN
IN Group use or not
G.LOCK
LOCK Group use or not
Menu
Code
Parameter
Setting Range
Display Condition
Default
Value
AT. MD
Auto Tuning Mode Selection
STD, LOW *1
AUTO & PID
STD
AT
Auto Tuning
OFF, ON, Auto (*2)
AUTO & PID제어시
OFF
8-2. Operating Menu (OPER)
●
Auto tuning Group (G.AT) : Only display when program operation status
● PID Group (G.PID)
✽1 ; Low : Auto Tuning Starts as -10% of SV ✽2 Auto is displayed when LEVEL=ON in Control Group
Menu
Code
Parameter
Setting Range
Display
Condition
Default
Value
ARW
Anti - Reset Wind up
AUTO, 50.0 ~ 200.0 %
PID Control
50.0
ALPHA Alpha
0 ~ 100
PID Control
50
PIDSL
PID Group Select
0 ~ 4 (Set 1 ~ 4 to move to next parameter)
PID Control
0
n.P
Proportional band
0.1 (H/C Type : 0.0) ~ 999.9 %
PID Control
5.0 %
n.I
Integral time
OFF / 1 ~ 6000 s (Sec.)
PID Control
240 s
n.D
Derivative time
60 s
n.MR
Manual reset
-0.5 ~ 105.0 % (%)
I = OFF
50.0%
n.Pc
Proportional band of cooling side 0.0 (ON/OFF control) / 0.1 ~ 999.9 %
HC TYPE
5.0 %
n.Ic
Integral time of cooling side OFF / 1 ~ 6000 s
240 s
n.Dc
Derivative time of cooling side OFF / 1 ~ 6000 s
60 s
n.DB
Dead band of Heating-Cooling side -100.0 ~ 50.0 %
3.0 %
n.LVL
PID Level n
EU (0) ≤ 1.LVL ≤ 2.LVL ≤ EU (100 %) (EU) LEVEL = ON EU (100%)
LVLD
Reference DEV
OFF / EUS (0 ~ 100 %) (EU)
LEVEL = ON EUS (0.5%)
●
Quick Menu Group (G.QUICK)
● Using of Auto Tuning
- Please do not use Auto Tuning as following controls
- Quick response controller such as flow control and press control
- Controller output should not be ON /OFF even for a short time.
- Controller should not have big load to the control part
- Fluctuation of set value gives bad effect on product quality
Caution