Alarm-3 setpoint (AL 3)
•Initial value : Maximum value of range (refer to input type and range code table)
•Setting range : Range (refer to input type and range code table)
•Description : Please set the set value of alarm 3
It does not appear if there is no alarm option or the alarm type is FAIL
①
②
⑤
⑥
⑦
⑪
⑩
⑨
⑧
③
④
①
②
③
④
동작모드
동작모드
셋업모드
█
Proportional band (PB)
•Initial value : 30 ℃, 30.0 ℃,Voltage input : 3.0 %
•Setting range : 0(0.0) ~ Range maximun
•Description : Set the proportional band (PB) for P control, PI control, PD control, and
PID control.
It is automatically set when automatic calculation (AT) is executed.
①
②
⑤
⑥
⑦
⑪
⑩
⑨
⑧
③
④
①
②
③
④
동작모드
동작모드
셋업모드
█
Integral time (TI)
•Initial value : 60 second
•Setting range : 1 ~ 3600 second
•Description : Set the integral operation time
It is set automatically when automatic calculation (AT) is executed
①
②
⑤
⑥
⑦
⑪
⑩
⑨
⑧
③
④
①
②
③
④
동작모드
동작모드
셋업모드
█
Overintegration limit (AR)
•Initial value : 0 (Auto)
•Setting range : 0 (Auto) ~ 100 %
•Description : To prevent overshoot due to over-integration effect,
set the effective operating range of integral operation.
Set Ar = 0, it works automatically.
①
②
⑤
⑥
⑦
⑪
⑩
⑨
⑧
③
④
①
②
③
④
동작모드
동작모드
셋업모드
█
Derivative time (TD)
•Initial value : 60second
•Setting range : 1 ~ 3,600second
•Description : Set the differential operation time.
When automatic calculation (AT) is executed, it is set automatically.