background image

Multi Channel T

emper

atur
e c
ontr

oller

24

 

 Data length (DLN)

•Initial value : 7 
•Setting range : 7 ~ 8
•Contents : ·Set the communication data length.
                         ·Select the communication option and the 
                              parameters will be displayed.                                          
                           7 : 7 BIT              8 : 8 BIT

동작모드

동작모드

셋업모드

 

 Response time (RPT)

•Initial value : 0
•Setting range : 0 ~ 10
•Contents :  ·Set the communication response time.
                          ·Select the communication option and the  
                             parameters will be displayed.          
                        ·Response time = processing time + RPT×20 ㎳T

동작모드

동작모드

셋업모드

 

 Lock level(LOC 1)

•Initial value : 0000  
•Description :·A device that restricts parameter 
                              setting changes by key operation.
                            ·DIGIT 1 : All parameters except SV and alarm 1, 2, 3 are prohibited.  
                              0 : unlock               1 : lock
                            ·DIGIT 2: Setting of alarms 1, 2 and 3 is prohibited.
                                0 : unlock               1 : lock
                            ·DIGIT 3 : Prohibits setting of SV set value.
                               0 : unlock               1 : lock
                            ·DIGIT 4 : Disabled (fixed to "0")

동작모드

동작모드

셋업모드

 

 Lock level (LOC 2)

•Initial value : 0000
•Description :·It is a device that limits the prohibition of operation/stop 
change and the prohibition of change of zone area.
         ·DIGIT 1 : RUN/STOP change is prohibited.
         ·DIGIT 2 : Zone changes are prohibited.
         ·DIGIT 3 : Not used (fixed at "0")
         ·DIGIT 4 : Not used (fixed at "0")
            0 : unlock               1 : lock

동작모드

동작모드

셋업모드

 

 Scan time (SCAN)

•Initial value : 2 seconds
•Setting range : 1 ~ 100 seconds  
•Contents :  Set the time from the currently displayed 
                       channel to the next channel.

동작모드

동작모드

셋업모드

Содержание MC9 Series

Страница 1: ...troller operation manual Thank you very much for purchasing Hanyoung Nux products Please use the product according to the intended use after reading the operation manual to see if it is the product yo...

Страница 2: ......

Страница 3: ...4 Measured value PV set value SV display mode 3 5 Temperature setting value SV setting and display mode 3 6 Normal setting mode 3 7 Initial setting mode 3 8 Setting sequence 4 1 Set value SV change 4...

Страница 4: ...Repairs due to failure that occur after the warranty period of the product has expired will be handled at actual cost paid in accordance with the standards set by HANYOUNGNUX In the following cases e...

Страница 5: ...device and the system used in connection with this device please follow the safety precautions in this manual In case of use or handling not in accordance with the instructions of the user manual or a...

Страница 6: ...er the warranty period of the product has expired are handled at actual cost paid in accordance with the standards set by our company In the following cases even failures occurring within the warranty...

Страница 7: ...tional N None 3 AL2 AL3 RS485 422 contact input Power supply voltage 2 100 240 V a c 50 60 4 Channels 8Channels Model Code Description MC9 8 8Channel Digital Thermostat size 96 W X 96 H X 100 D Contro...

Страница 8: ...K 199 9 999 9 J0 J 200 1200 J1 J 199 9 999 9 E0 E 200 900 E1 E 199 9 900 0 T0 T 199 9 400 0 R0 R 0 1700 R1 R 0 0 999 9 B0 B 100 1800 B1 B 100 0 999 9 S0 S 0 1700 S1 S 0 0 999 9 L0 L 199 9 900 0 N0 N...

Страница 9: ...Communication 9 Before start Install Operation Function Communication 9 Before start Install Operation Function Communication Dimentions Panel cutout Unit mm External dimensions Panel cutout 96 0 8 0...

Страница 10: ...50 51 52 53 54 55 56 57 58 59 60 Connection diagrams Output 1 4 Output 5 8 Output 6 Output 5 Output 7 Output 8 Relay SSR Current output 53 54 Relay SSR Current output 55 56 Relay SSR Current output 57...

Страница 11: ...8 Channels Channels 8 Channels 7 Channels 6 Channels 5 V d c T C RTD A B C 25 26 27 V d c T C RTD A B C 28 29 30 V d c T C RTD A B C 31 32 33 V d c T C RTD A B C 34 35 36 V d c T C RTD A B C 13 14 15...

Страница 12: ...Up to 32 units can be connected Be sure to connect a terminating resistor 100 200 1 4 W at both ends of the communication path Terminating Resistance Terminating Resistance Terminating Resistance Ter...

Страница 13: ...atic scan When CH is pressed during individual scan the channel to be scanned is changed Save the changed parameter or move to the next parameter Move the number of digits of the set value Press for 1...

Страница 14: ...0 120 91 5 0 8 0 0 91 5 0 8 0 0 96 96 96 96 8 74 2 100 96 96 96 96 96 96 Input type and Range display When power is applied the input type and range are displayed for about 2 seconds and then the moni...

Страница 15: ...OFF 0 1 200 0 minute 8 0 Minute O O Loop break alarm hysteresis EUS 0 100 EUS 0 EUS O O Alarm 1 setpoint 5 3 Alarm action reference O O Alarm 2 setpoint O O Alarm 3 setpoint O O Proportionality EU 0 1...

Страница 16: ...tage range to indicate the measurement range and EUS is the span for the range indicated with the percentage range to indicate the measurement range EU Engineering Unit EUS Ex EU EUS setting range whe...

Страница 17: ...V SV mode it can switch between RUN operating STOP stop and measured value displays STOP when operation is stopped and displays error message code when an error occurs Temperature setpoint SV setting...

Страница 18: ...er the General setting mode In this setting mode it is a parameter setting mode in which the user frequently changes the setting value and it can be saved in up to 8 memory zones When setting can be r...

Страница 19: ...ional band PB for P control PI control PD control and PID control It is automatically set when automatic calculation AT is executed Integral time TI Initial value 60 second Setting range 1 3600 second...

Страница 20: ...ted If AT is executed while slope setting RATE is running RATE is immediately stopped and automatic calculation is executed with the newly set set value Select whether to use contact input DISL Initia...

Страница 21: ...e standard value it is compensated for by the deviation to match Initial value OFF Setting range OFF ON Set whether to execute auto tuning Auto tuning execution After turning on the AT parameter press...

Страница 22: ...escription Set the control output cycle It does not apply when the output type is current Alarm 3 type ALT 3 Initial value 0 Setting range 0 16 Description Set the type of alarm 3 Please refer to 5 3...

Страница 23: ...communication stop bit Select the communication option and the parameters will be displayed 1 1 BIT 2 2 BIT Parity bit PRI Initial value 0 Setting range 0 2 Description Set communication parity Select...

Страница 24: ...ng changes by key operation DIGIT 1 All parameters except SV and alarm 1 2 3 are prohibited 0 unlock 1 lock DIGIT 2 Setting of alarms 1 2 and 3 is prohibited 0 unlock 1 lock DIGIT 3 Prohibits setting...

Страница 25: ...pressed once in PV SV display mode the SV set value setting mode is displayed as shown on the right 2 Press the 8 74 26 100 120 120 91 5 0 8 0 0 91 5 0 8 0 0 96 96 key once and the first digit 9 of S...

Страница 26: ...imes as shown below and the 100 digit number will flash Press the 8 74 26 100 120 120 91 5 0 8 0 0 91 5 0 8 0 0 96 96 key twice to change to In the SV display window it is changed to 100 as shown in t...

Страница 27: ...0 0 0 0 3 Press the CH key once to change the channel number from 1 to 2 This will change the channel number from 1 to 2 4 To change the set value SV of channel number 2 from 200 to 100 Press the 8 7...

Страница 28: ...2 The letter A here stands for batch setup Each time the CH key is pressed the channel number changes as follows 1 2 3 4 5 6 7 8 A 3 Press the 8 74 26 100 120 120 91 5 0 8 0 0 96 96 key to move the c...

Страница 29: ...the 8 96 96 key again to display the memory area setting mode That is whenever the 8 74 26 100 120 120 96 96 key is pressed in the temperature measurement mode Temperature measurement mode Temperatur...

Страница 30: ...mory area there is a method by operating the front key in addition to the method by external contact input option and communication option The method by external contact input and the method by front...

Страница 31: ...arameters such as temperature set value SV of channels 1 to 8 in 8 memory zones In other words data of 8 channels is stored in one memory zone and temperature control is possible under different setti...

Страница 32: ...he measured values and set values of all channels in the memory zone at scan time intervals For example if the scan interval time is set to 2 seconds the measured value and set value of each channel a...

Страница 33: ...be set within the range of 1999 to 9999 Setting range and initial setting value for each alarm type Setting number Alarm type Setting range Initial value 0 No alarm 1 Deviation setting High limit ala...

Страница 34: ...ALM ON OFF ON OFF SV ON OFF ALM SV ON OFF ALM ON OFF ALM ON OFF SV temperatur low temperature High temperature low temperature High temperature low temperature High temperature low temperature High t...

Страница 35: ...put is 100 and the control output operation is a direct operation It operates when the measured value does not fall more than 2 2 2 within the time set in LBA When output is 100 and control output ope...

Страница 36: ...put status Normal operation PV status Normal operation In case of EEPROM error Display current PV value Countermeasure POWER OFF ON Output status Normal operation PV status Normal operation Input sens...

Страница 37: ...age Scaling 0 0 100 0 of F S Input correction 100 of F S Reference point compensation error 1 5 Between 0 and 50 C Input open circuit detection UP SCALE reverse acting DOWN SCALE reverse acrion Insula...

Страница 38: ...sistance 300 Three axes in each direction Three times each Weight g 700 g Title Description Applied specification EIA RS485 RS422A Maximum number of connections 31 or 255 units Communication method 2...

Страница 39: ...ustomer cannot change it 5 Q I want to use the output together with relay or ssr depending on the channel Is it possible A This control instrument can be used separately up to two types of 1 4 channel...

Страница 40: ...to enter the setup mode and press ENT KEY to enter it in the parameter of FILT the movement appears dull 17 Q How many PID values operate in channel 8 A The PID value constant exists in each channel 8...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ......

Страница 45: ...MA0401E220517_U 28 Gilpa ro 71beon gil Michuhol gu Incheon korea Tell 82 32 876 4697 E mail ovterseas hynux com http www hanyoungnux com MC9...

Отзывы: