37
Be
for
e s
tart
Ins
tall
Oper
ation
Func
tion
Communic
ation
█
Output specification
█
Input specifications
▍
Specification
Title
Description
Temperature input
(multi input)
Thermocouple (T.C) : K, J, R, S, B, E, N, T, W, PL2, U, L
RTD (R.T.D) : Pt100 Ω, KPt100 Ω
Direct current voltage (DCV) : 0 ~ 5 V, 1 ~ 5 V, 0 ~ 10 V,4 ~ 20 ㎃
(250 Ω with external resistor)
The degree of display level
Thermocouple : ±(0.3 % of F.S ±1Digit) or ±2 °C, whichever is greater
RTD : (±0.3 % of F.S ±1Digit) or ±0.8 °C, whichever is greater
DC voltage : ±0.3 % of F.S ±1Digit
Sampling cycle
1 second
Input display resolution
Basically, below the decimal point of the "measurement range index"
Input impedance
1 ㏁ or more. (Input thermocouple and DC voltage)
Effect of allowable input
resistance
about 0.2 ㎶/Ω
Acceptable input wire
resistance
Temperature resistance
(10 Ω or less. However, the resistance between the three lines will be the sam)
Acceptable input voltage
Within 2–5 V (thermal band, thermoelectric resistor), within -5–12 V (d. c. voltage)
Scaling
0.0 % ~ 100.0 % of F.S
Input correction
±100 % of F.S
Reference point
compensation error
±1.5 ℃ (Between 0 and 50°C)
Input open circuit detection UP SCALE (reverse acting), DOWN SCALE (reverse acrion)
Insulation resistance
20 ㏁ or morte (500 V d.c.), Measurement terminal-Power terminal
Voltage resistance
2,300 V a.c. 50/60 ㎐, For a minute. Measurement terminal-Power terminal.
Title
Description
Control
output
Relay output
Contact capacities: 1a, 250Va.c., 3A. (resistance load)
Proportional cycle: 1 to 1,000 seconds
Time resolution: 0.1 % or 10 ms, whichever is smaller
S.S.R
(voltage pulse)
(voltage pulse) Voltage pulse : More than or equal to about 12 V d.c. (Load resistance
of 600 이상 or more)
Proportional cycle: 1 to 1,000 seconds
Time resolution: 0.1% or 10%, whichever is smaller
S.C.R
(Current.)
Current. : 4-20 ㎃ d.c., 0 ~ 20 ㎃ (Load resistance less than 600Less than)
Degree : ±1.0 % of F.S (4-20 ㎃ range)
Alarm
output
(Relay)
Temperature
alarm
(AL1,2,3)
1a, 250 V a.c., 1 A. 30 V d.c. 1 A (Resistance load)
Output score: Up to 3 points (depending on the selection specification)
Short-loop
warning
(L.B.A)
1a 1point, 250 V a.c., 1 A. 30 V d.c. 1A (Resistance load)
Proportional period : 1 ~ 1,000 seconds