Range
Span
-200 ~ 1,370
1,570
0 ~ 1,370
1,370
50 ~ 1,350
1,300
4 ~ 20 ㎃
16 ㎃
The Range is the range of the minimum and maximum values of the input variable or output variable,
and is displayed as “minimum value to maximum value”.
The Span is the difference between the maximum and minimum values of a range.
That is, when the range is “-200 ~ 1,370”, The span would be 1,370 - (-200) = 1,570
█
Range & Span
Display items
Setting range (℃)
Note
EU 0 ~ 100 %
-200 ~ 1370
Percentage range display for range
EU -100 ~ 100 %
-1770 ~ 1370
EUS 0 ~ 100 %
0 ~ 1570
Show percentage range for span
EUS -100 ~ 100 %
-1570 ~ 1570
EU (Engineering Unit) refers to the industrial unit, and The range is indicated with the percentage range to indicate
the measurement range, and EUS is the span for the range indicated with the percentage range to indicate the
measurement range.
█
EU (Engineering Unit) & EUS
Ex) EU, EUS setting range when the range is “-200 ℃ ~ 1370 ℃”
■
Initial setting mode
Signal
Name
Range
Initial Value
Unit
Memory zone
Channel
Auto tuning
(A.T)
OFF, ON
OFF
ABS
O
O
Temperature
compensation
0.0 ~ 100 %
0.0
EUS
X
O
Upper limit range
FR-L ~
upper limit range
Input range
upper limit
EU
X
X
lower limit range
upper limit range
~ FR-H
Input range
lower limit
EU
X
X
Alarm-1 type
0 ~ 16
0
-
X
X
Alarm-2 type
0 ~ 16
0
-
X
X
Alarm-3 type
0 ~ 16
0
-
X
X
Filter
OFF, 1 ~ 100
OFF
Second
X
O
Proportional cycle
1 ~ 100
20/2
Second
X
O
Address
1 ~ 99
1
ABS
X
X
Protocol selection
0 ~ 1
0
-
X
X
Communication
speed
0 ~ 3
3
ABS
X
X
Parity bit
0 ~ 2
0
ABS
X
X
Stop bit
1.2
1
ABS
X
X
Data length
7.8
8
ABS
X
X
Response time
0 ~ 10
O
ABS
X
X
Scan time
1 ~ 10
2
Second
X
X
Lock 1
LOC 1 reference
0000
ABS
X
X
Lock 2
LOC 2 reference
0000
ABS
X
X