HAMWORTHY HEATING LTD
34
SPETISBURY
500001118/C
110
150
220
280
340
GENERAL DATA
No. OF SECTIONS
5
6
8
10
12
BOILER INPUT - maximum
kW
125.5 171.2 250.5 309.9 377.9
(nett) 34.06 MJ/m
3
Btu/hr x 1000
428.2 584.1 854.7 1057 1289
BOILER INPUT - maximum
kW
139.37 190.1 278.2 344.0 419.4
(gross) 37.8 MJ/m
3
Btu/hr x 1000
475.5 648.6 949.2 1174 1431
BOILER OUTPUT - maximum
kW
110
150
220
280
340
Btu/hr x 1000
375
511
751
955
1160
FLUE DATA
NOMINAL FLUE DIA.
mm
180
in
7
FLUE DRAUGHT REQUIRED
mbar
0.1 - 0.3
AT BOILER OUTLET
in.wg.
0.04 - 0.12
COMBUSTION CHAMBER
mbar
2.8
5.0
5.9
3.9
5.5
RESISTANCE (maximum)
in.wg.
1.1
1.96
2.32
1.54
2.17
APPROX. FLUE GAS TEMP (gross)
°C
225
APPROX. FLUE GAS VOLUME
m
3
/h
174
236
294
383
467
@ NTP (wet)
ft
3
/h
6144 8333 10381 13532 16501
GAS DATA
NOMINAL GAS INLET PRESSURE
mbar
20
MAXIMUM GAS INLET PRESSURE
mbar
25
GAS FLOW RATE
m
3
/h
13.3
18.2
26.5
32.8
39.9
ft
3
/h
469.5
642.5 935.5 1157 1410
GAS INLET CONNECTION
Rc ¾”
Rc 1”
Rc 1¼”
WATER DATA
WATER CONNECTIONS - FLOW &
RETURN
4 in N.B.
MAXIMUM WATER
bar g.
5.0
PRESSURE
psi g
73.0
WATER CONTENT
litres
78
92
120
148
176
UK gal.
17.2
20.3
26.4
32.6
38.8
BOILER WEIGHT (FULL)
kg
508
592
755
923
1106
WITHOUT BURNER
lb
1118 1302 1661 2031 2433
BURNER WEIGHT
kg
27.6
27.6
27.6
47.6
47.6
(including packaging)
lb
61
61
61
105
105
PRESSURE SWITCH SETTING
mbar
0.3
0.2
0.4
1.3
1.4
MAX WATER TEMP.
100
°
C
(TEMP LIMITER SET AT
°
C)
ELECTRICAL SUPPLY
230V 1ph ~ 50Hz
BOILER MODEL - Spetisbury
Figure 15.7 – Performance and General Data Information (Natural Gas)
Note:
For matched burner/boiler combinations, refer to Figure 15.7
For combustion target figures, refer to Figure 11.1
GENERAL INFORMATION